1.7.7 Wiring the Totalizer/ Frequency Outputs

The GF868 can accommodate 1 to 6 totalizer/frequency outputs option cards. Each totalizer/frequency outputs option
card provides four outputs (A, B, C, and D) that can be used as either totalizer or frequency outputs.
Each totalizer/frequency output requires two wires. Wire this terminal block in accordance with the pin number
assignments shown in Figure 9 on page 18. Figure 7 shows sample wiring diagrams for the totalizer/frequency outputs.

1.7.8 Wiring the RTD Inputs

The GF868 can accommodate 1 to 6 RTD (Resistance Temperature Device) inputs card(s). Each RTD inputs card
provides two direct RTD inputs (A and B).
Each RTD input requires three wires. Feed the wires through one of the conduit holes on the bottom center of the
enclosure. Connect the wires to the 8-pin RTD inputs option card terminal block as shown in Figure 9 on page 18.
DigitalFlow™ GF868 Startup Guide (1 and 2-Channel)
Totalizer Output
Model GF868
Max. Current: 4A
Max. Voltage: 150V
Isolation Voltage: 500V
Max. Load Power: 10W In
NO
C
C = Isolated Return
Frequency Output
Model GF868
+5V
200
NO
C
C = Isolated Return
Figure 7: Totalizer/Frequency Output Wiring
Pulse Counter
Volts +
(Int. Pwr. Sup.)
Load
Volts –
(Common)
Frequency Counter
IN
Common
Chapter 1. Installation
15