Hardware Arrangement
The coils and contacts in electromagnetic contacts and relays in an external circuit are sources of
noise. Do not install them close to the Panel PC. Locate them at least 100 mm away from the Panel
PC.
DC I/O
device
Terminal block
Example of Arrangement in Panel
Wire Layout for the Power Supply
Observe the following points when wiring the power supply system.
• Separate the Panel PC power supply from the I/O device power supply and install a noise filter near
the Panel PC power supply feed section.
• Use an isolating transformer to significantly reduce noise between the Panel PC and the ground. In-
stall the isolating transformer between the Panel PC power supply and the noise filter, and do not
ground the secondary coil of the transformer.
• Keep the wiring between the transformer and the Panel PC as short as possible, twist the wires well,
and keep the wiring separate from high-voltage and power lines.
Power Supply System Diagram
NY-series Industrial Panel PC Hardware User's Manual (W557)
OMRON
product
AC I/O
device
Power circuits
Power supply for general operations circuits
I/O power supply for Omron product
I/O power supply for Omron product
Noise
Unit power supply for Omron product
filter
Outlet (for peripheral devices)