Binary Inputs - Grundfos CIU 300 Functional Profile And User Manual

Bacnet ms/tp for hydro mpc, control mpc and multi-e
Table of Contents

Advertisement

6.2 Binary inputs

Binary objects that provide information from the Grundfos booster.
ID
Object Name
BI, 0
Control source status
BI, 2
Rotation status
BI, 3
At minimum speed
BI, 4
At maximum speed
BI, 5
Standby pumps active
BI, 6
Pressure relief active
BI, 7
Soft pressure active
BI, 8
Low flow boost active
BI, 9
Low flow stop active
BI, 10
Alternative setpoint active
BI, 11
Digital input 1 status
BI, 12
Digital input 2 status
BI, 13
Digital input 3 status
BI, 14
Digital output 1 status
BI, 15
Digital output 2 status
BI, 16
Subpump 1 presence
BI, 17
Subpump 1 communication status
BI, 18
Subpump 2 presence
BI, 19
Subpump 2 communication status
BI, 20
Subpump 3 presence
BI, 21
Subpump 3 communication status
BI, 22
Subpump 4 presence
BI, 23
Subpump 4 communication status
BI, 24
Subpump 5 presence
BI, 25
Subpump 5 communication status
BI, 26
Subpump 6 presence
BI, 27
Subpump 6 communication status
BI, 28
Fault simulation status
12
R/W
Notes
Status of the actual control source.
R
0 = Local control
1 = Bus control.
Rotation status.
R
0 = No rotation
1 = Rotation (one or more pumps running).
0 = Not running at minimum speed
R
1 = Running at minimum speed.
0 = Not running at maximum speed
R
1 = Running at maximum speed.
0 = Standby pumps not active
R
1 = Standby pumps active.
0 = Pressure relief not active
R
1 = Pressure relief active.
0 = Soft pressure not active
R
1 = Soft pressure active.
0 = Low flow boost not active
R
1 = Low flow boost active.
0 = Low flow stop not active
R
1 = Low flow stop active.
0 = Alternative setpoint not active
R
1 = Alternative setpoint active.
0 = Not active
R
1 = Active.
0 = Not active
R
1 = Active.
0 = Not active
R
1 = Active.
0 = Not active
R
1 = Active.
0 = Not active
R
1 = Active.
0 = Subpump not present
R
1 = Subpump present.
0 = Communication OK
R
1 = Communication fault.
0 = Subpump not present
R
1 = Subpump present.
0 = Communication OK
R
1 = Communication fault.
0 = Subpump not present
R
1 = Subpump present.
0 = Communication OK
R
1 = Communication fault.
0 = Subpump not present
R
1 = Subpump present.
0 = Communication OK
R
1 = Communication fault.
0 = Subpump not present
R
1 = Subpump present.
0 = Communication OK
R
1 = Communication fault.
0 = Subpump not present
R
1 = Subpump present.
0 = Communication OK
R
1 = Communication fault.
Fault simulation status.
R
0 = Fault simulation disabled
1 = Fault simulation enabled.
Multi-E
MPC
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X