Object Overview; Device Object - Grundfos CIU 300 Functional Profile And User Manual

Bacnet ms/tp for hydro mpc, control mpc and multi-e
Table of Contents

Advertisement

6. Object overview

6.1 Device Object

The following properties are supported in the Device Object (available for all booster types).
Property identifier
Object_Identifier
Object_Name
Object_Type
System_Status
Vendor_Name
Vendor_Identifier
Model_Name
Firmware_Revision
Application_Software_Version
Location
Description
Protocol_Version
Protocol_Revision
Protocol_Services_Supported
Protocol_Object_Types_Supported BACnetObjectTypesSupported
Object_List
Max_APDU_Length_Accepted
Segmentation_Supported
APDU_Timeout
Number_Of_APDU_Retries
Max_Master
Max_Info_Frames
Device_Address_Binding
Database_Revision
Data type
BACnetObjectIdentifier
CharacterString
BACnetObjectType
BACnetDeviceStatus
CharacterString
Unsigned16
CharacterString
CharacterString
CharacterString
CharacterString
CharacterString
Unsigned
Unsigned
BACnetServicesSupported
BACnetARRAY[N]of
BACnetObjectIdentifier
Unsigned
BACnetSegmentation
Unsigned
Unsigned
Unsigned
Unsigned
List of BACnetAddress-Bindings Holds address bindings to other devices, if any.
Unsigned
Notes
3.5 Selecting the Device Object Instance
See section
Number
.
3.6 Selecting the Device Object Name
See section
DEVICE.
OPERATIONAL.
Grundfos.
227.
Will show the Grundfos booster model to which the
CIM/CIU 300 is connected.
Revision of the firmware in the CIM/CIU 300.
Software build date, DD-MM-YYYY.
The user can enter a location here
(maximum 200 characters).
The user can enter a description here
(maximum 200 characters).
Actual version of the BACnet protocol.
Actual revision of the BACnet protocol.
Indicates which standardised protocol services are
supported.
Indicates which standardised protocol object types are
supported.
An array of objects available.
The maximum number of bytes that may be contained in
a single APDU. Fixed to 480.
Indicates if segmentation of messages is possible.
Will always read NO_SEGMENTATION.
Indicates the amount of time in ms before timeout.
Maximum number of times an APDU is to be retransmitted.
Specifies the highest possible MAC address for master
nodes and must be between 1 and 127.
The default value is 127, but this value can be lowered by
the user.
The Max_Master value must be higher than or equal to the
highest MAC address used by a master node in an MS/TP
network.
Specifies the maximum number of information frames that
are sent before the token is passed on. Fixed to 1.
Logical revision number for the device database.
Access
R
.
W
R
R
R
R
R
R
R
W
W
R
R
R
R
R
R
R
R
R
W
R
R
R
11