Installing and setting the option with tact switch and functions
1. Press and hold K2 for 3 seconds. (Only available when the operation is stopped)
- The display will show the following.
- If you have set the Emergency operation for compressor malfunction, 1 or 2 will be displayed on Seg 4.
- Seg 1 and Seg 2 will display the number for selected option.
- Seg 3 and Seg 4 will display the number for set value of the selected option.
2. If you have entered option setting, you can shortly press the K1 switch to change the value of the Seg 1 and Seg 2 to select desired option.
- Refer to the table for the Seg number of the function for each option.
3. If you have selected desired option, you can shortly press the K2 switch to change the value of the Seg 3 and Seg 4 to change the functional
setting for the selected option.
- Refer to the table for the Seg number of the function for each option.
4. After selecting the function for options, press and hold the K2 switch for 2 seconds.
Entire 7-segment will blink to begin tracking mode and value of the option will be be saved. If you do not end the setting mode properly,
option will not be saved.
Option item
Input unit
Emergency
operation for
Individual
compressor
malfunction
Unused option
Main
Unused option
Main
Unused option
Individual
Oil collection
Main
interval
Temperature to
trigger defrost
Main
operation
Outdoor unit fan
Individual
speed correction
Unused option
Main
Unused option
Main
Unused option
Main
Unused option
Main
Unused option
Main
Unused option
Main
Unused option
Main
SEG1
SEG2
SEG3
SEG4
0
0
0
1
0
0
0
2
0
1
0
0
0
2
0
0
0
3
0
0
0
0
0
4
0
1
0
0
0
5
0
1
0
0
0
6
0
1
0
7
0
0
0
8
0
0
0
9
0
0
1
0
0
0
1
1
0
0
1
2
0
0
1
3
0
0
138
Function of the option
Disabled
Set compressor 1 as
malfunction state
Set compressor 2 as
malfunction state
Unused option
Unused option
Unused option
Factory default
Shorten the interval by 1/2
Factory default
Apply setting when the
product is being installed in
humid area such as near river
or lake
Factory default
Increase fan speed
Unused option
Unused option
Unused option
Unused option
Unused option
Unused option
Unused option
Remarks
E560 will occur when all the
compressors are set as malfunction
state.
Increase the outdoor unit fan
speed to maximum value