8-2. How to set hydro controller option

Operation On/Off input method
Temperature setting input method
1. Turn on the product.
2. Press and hold the K2 to enter the option setting.
- In option setting, other key input (forced fan, temperature setting, etc.) is not received.
3. Press K1 shortly to display the number for selected option.
4. Press K2 shortly to display the number for set value of the selected option.
5. Finish the option setting.
- Press K2 long to finish the setting with all option values determined and saved.
- Press K1 long to finish the setting with all option values cancelled and keep the values as before entering the setting.
• In option setting, press K4 long to initialize all option values.
No.
Option item
1
Operation On/Off input method
Temperature setting input
2
method
Operation mode (Cool/Heat,
3
normal/hot water) input method
4
Demand control input method
5
Demand level
6
Quiet function input method
7
Forced fan function input method
8
Water law input method
9
Pump operation when thermo off
10
Remote error reset input
Setting address of Chiller Unit
- Module must be designated
when it is installed.
11
(Refer to Module-Controller
Installation Manual)
Option No.
SEG1
SEG2
0
1
0
2
Option
Factory
Option
value
default
0
Module control/DMS
0.1
0
1
External contact
0
Module control/DMS
0.1
0
1
External contact
0
Module control/DMS
0.1
0
1
External contact
0
Module control/DMS
0.1
0
1
External contact
0
Default (100 %)
1
95 %
2
90 %
3
85 %
4
80 %
5
75 %
0 ~ 11
3
6
70 %
7
65 %
8
60 %
9
55 %
10
50 %
11
Not applied (No limit)
0
Module control/DMS
0.1
0
1
External contact
0
Module control/DMS
0.1
0
1
External contact
0
Module control/DMS
0.1
0
1
External contact
Pump OFF when thermo OFF and
0
operation pattern is not standard control
0.1
0
1
Pump ON always when thermo OFF
0
Disuse
0.1
0
1
Use
0 ~ 15
0
Setting unit address
132
Option value
SEG3
SEG4
-
-
-
-
Definition
Main unit of group
Main unit of group
Main unit of group
Main unit of group
Main unit of module
Main unit of group
Main unit of group
Main unit of group
Main unit of module
Main unit of module
SEG5
SEG6
-
0
-
0
Module control
Setting unit
setting option
Note1)
Note2)
Note2)
Note2)
Note2)
0
Note2)
Note2)
Note2)
Each unit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents