Low Pressure Sensor Error (Open / Short) - Samsung AG042KSVANH Service Manual

System air conditioner dvm chiller
Hide thumbs Also See for AG042KSVANH:
Table of Contents

Advertisement

4-3-14. Low pressure sensor error (Open / Short)

Inverter / Hydro control part display
Judgment Method
Cause of problem
1. Low Pressure sensor Open/Short error determination method
1) Identifies from when power is supplied or 2 minutes after RESET, and only when set is stopped.
2) An Open/Short error will occur if the input voltage standard range of 0.5V ~ 4.95V is exceeded.
2. Inspection Method
Did the Low Pressure sensor connector
get disconnected from the PCB?
Is there refrigerant inside the set?
(Please check by connecting the menu
folder gauge to the service valve)
Out of the PCB Low Pressure
sensor terminals, is there voltage between
pins 3 and 4 5V?
Replace Low Pressure sensor
Refer to the inspection method below.
Disconnection or breakdown of relevant sensor.
Yes
Yes
Yes
No
No
No
54
Please re-inspect after connecting
the connector to the PCB
Refill refrigerant after vacuum
Replace PCB
The
mark is the 1st pin on the PCB.