11
Line redundancy (1 ASIC oper.)
GSD-File: DREM0C27
6
Redundancy response (only if S6.4 and S6.5 = 1)
0
Redundancy reply on active channel
1
Redundancy reply on both channels
7
Position output Profibus
0
Output limited to 0..1000 or 46..230
1
Output with over- / underflow
4.4 Diagnosis LED's
4.4.1 LED 1V8, 3V3 und 5V1
These LED group indicates the presence of the different supply voltages. For accurate operation
the presence of all voltage levels is essential. If one or more of these LED's are off, this indicates
a serious damage.
4.4.2 LED BL
The LED indicates the correct program execution flow with a flash rate of 1Hz. If the LED keeps
off the user program is not executed. In this case the interface board either is malfunctioning, the
Firmware is missing or the Bootloader mode for firmware download is activated.
4.4.3
LED H16 DIAG
The LED indicates possible failures by flashing with two different frequencies. If the LED is off no
failure is recognized by the controller logic.
If more than one failure is recognized always the failure with the lowest group / code will be
signalled.
Flash code
Fast flash
First slow sequence
Second slow sequence
Start
DREHMO - MaticC Profibus DPV0/DPV1
Complementary operating manual
Line redundancy
GSD-File: DREM0C27
Start of sequence
Failure group
Failure code
Failure group
Failure code
Page 15 of 28
Need help?
Do you have a question about the c-matic and is the answer not in the manual?