may result in potential failures or protecting function loss, even directly
damage the load, battery or UPS.
The detail description shows in the next table.
Description
User password
Audio alarm
Output voltage
Output frequency
Power strategy
DC start
Site wiring fault
alarm
Ambient
temperature
warning
Automatic battery
tests period
Auto restart
Automatic
overload restart
Auto bypass
Short circuit
clearance
Available Settings
<enable><disable>
If enable, you must enter an correct
password.
<enable><disable>
If disable, all alarm is mute
<208V><220V> <230V> <240V>
<50HZ><60HZ>
< Auto-sensing>
<normal>
<high efficiency><converter>
<enable><disable>
Cold start
<enable><disable>
<enable><disable>
<0>.......<31days>
If select 0, Automatic battery test is disable.
<enable><disable>
Enabled means UPS will auto restart to
normal mode while utility recover after the
UPS has been shutdown for battery low.
<enable><disable>
Enabled
means
bypass mode to normal mode after over
load disappears.(Recover to 70%)
<enable><disable>
enabled means UPS will have bypass
output when utility power on.
Disabled means UPS will not have bypass
output when power on but could get bypass
output when UPS is fault or overload.
<enable><disable>
If enable, inverter continues output for 4S,
if output voltage recover to more than 50
percent of rating voltage, UPS stay on the
39
UPS
transfer
from
Default Setting
disable
enable
230V
<50HZ>
Normal
enable
disable
enable
7days
enable
enable
disable
disable