R36PEVLK + FDM36PEVLK
Outdoor
Unit
PE
L
N
L1
N1
C
Y
POWER 220V ~ 60HZ
(1) Power Cord 3 × 6.0mm² (H07RN-F)
(2) Power Cord 3 × 1.0mm² (H07RN-F)
(3) Communication Cords 2 × 1.0mm² (H07RN-F)
Capability of Breaker: 32A
R42PETLK + FDM42PEVLK
R48PETLK + FDM48PEVLK
Outdoor
Unit
L1
L2
L3
N
L
N
C
Y
POWER 220V 3 ~ 60HZ
(1) Power Cord 4 × 6.0mm² (H07RN-F)
(2) Power Cord 3 × 1.0mm² (H07RN-F)
(3) Communication Cords 2 × 1.0mm² (H07RN-F)
Capability of Breaker: 32A
42
(1)
PE
breaker
L
N
L
N
(2)
Indoor
Unit
C
R
Y
O
(3)
B
(1)
breaker
L1
L2
L3
PE
Indoor
(2)
Unit
L
N
C
R
Y
O
(3)
B
RY36PEVLK + FDYM36PEVLK
Outdoor
(1)
Unit
PE
L
N
L1
N1
(2)
C
R
Y
O
(3)
POWER 220V ~ 60HZ
(1) Power Cord 3 × 6.0mm² (H07RN-F)
(2) Power Cord 3 × 1.0mm² (H07RN-F)
(3) Communication Cords 4 × 1.0mm² (H07RN-F)
Capability of Breaker: 32A
RY42PETLK + FDYM42PEVLK
RY48PETLK + FDYM48PEVLK
Outdoor
Unit
(1)
L1
L2
L3
N
(2)
L
N
C
R
Y
O
(3)
POWER 220V 3 ~ 60HZ
(1) Power Cord 4 × 6.0mm² (H07RN-F)
(2) Power Cord 3 × 1.0mm² (H07RN-F)
(3) Communication Cords 4 × 1.0mm² (H07RN-F)
Capability of Breaker: 32A
PE
breaker
L
N
L
N
Indoor
Unit
C
R
Y
O
B
breaker
L1
L2
L3
PE
Indoor
Unit
L
N
C
R
Y
O
B