TROUBLESHOOTING

This section provides the required flow charts to troubleshoot
problems that may arise.
NOTE: Information required in the diagnoses can be found
either on the wiring diagrams or in the appendix.
Required Tools:
The following tools are needed when diagnosing the units:
S Digital multimeter
S Screw drivers (Phillips and straight head)
S Needle- -nose pliers
Recommended Steps
1. Refer to the diagnostic hierarchy charts below and
determine the problem at hand.
2. Go to the chart listed in the diagnostic hierarchy and follow
the steps in the chart for the selected problem.
INDOOR UNIT DIAGNOSTIC CODES
No.
Malfunction
Open or short circuit of
1
T1 temperature sensor
Open or short circuit of
2
T2 temperature sensor
3
Indoor EEPROM
4
Water- -level alarm
Refrigerant leakage
5
detection
O (on) X(off) ☆(flash at 5Hz) ◎(flash at 0.5Hz)
NOTE:
For problems requiring measurements at the control boards please note the following:
For Heat Pump Units Only:
1. Always disconnect the main power.
2. When possible check the outdoor board first.
3. Start by removing the outdoor unit top cover.
4. Reconnect the main power
5. Probe the outdoor board inputs and outputs with a digital
multi- -meter referring to the wiring diagrams.
6. Connect the red probe to hot signal and the black probe to
the ground or negative.
7. Note that some of the DC voltage signals are pulse and
gives continuously variable readings.
Table 17 – Fault Codes
Running lamp
Timer lamp
X
X
X
X
X
For ease of service, the indoor unit is equipped with diagnostic code
display LEDs in the indoor units. This diagnostic display is a
combination of flashing LEDs on the display panel or the front of the
unit. If possible, always check the diagnostic codes displayed on the
indoor unit. Once a failure occurs with the indoor unit in operation,
the green LED on the indoor unit flashes at intervals of 0.5 seconds.
The fault code is deduced from the number of times the green LED
flashes, blocking unit operation. Between one flash cycle and the next
one, a pause of 3 to 4 seconds elapses.
The diagnostic codes for the indoor units are listed in the appendix.
Problems may occur that are not covered by a diagnostic code,
however are covered by the diagnostic flow charts. These problems
are typical air conditioning mechanical or electrical issues that can
be corrected using standard air conditioning repair techniques.
Defrosting lamp
Alarm lamp
X
X
X
X
X
X
X
X
For Cooling only and Heat Pumps
1. If it is necessary to check the indoor unit board you must
start by disconnecting the main power.
2. Next remove the front cover of the unit and then control
box cover.
3. Carefully remove the indoor board from the control box,
place it face up on a plastic surface (not metal).
4. Reconnect the main power and repeat steps 5, 6, and 7.
5. Disconnect main power before reinstalling board to avoid
shock hazard and board damage.
19
Display
(digital tube)
E2
E3
E7
E8
EC