SAFETY CONSIDERATIONS Installing, starting up, and servicing air−conditioning equipment WARNING can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should ELECTRICAL SHOCK HAZARD install, start−up, and service this equipment. Failure to follow this warning could result in personal Untrained personnel can perform basic maintenance functions such injury or death.
PARTS LIST Table 1 – Parts List PART NAME INDOOR UNIT DRAIN ADAPTER AIR FILTER WIRED CONTROLLER WIRELESS REMOTE LITERATURE PACKAGE INCLUDING INSTALLATION INSTRUCTIONS AND WARRANTY CONDENSATE LIFT PUMP (EXTERNAL SIZES 09-18, INTERNAL SIZES 24-58) Air inlet Electric control cabinet Air filter Drain hose(field supplied) Air outlet...
SYSTEM REQUIREMENTS Allow sufficient space for airflow and servicing unit. See Fig. 6 for minimum required distances between the unit and the walls or ceilings. Piping IMPORTANT: Both refrigerant lines must be insulated separately. S Minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m). S Table 3 lists the pipe sizes for the indoor unit.
DIMENSIONS Air inlet from rear side Air filter 4-install hanger Test mouth & Test cover Outside air intake Electric control box 0.98in (25mm) Drain connecting pipe (for lift pump) 0.98in (25mm) Drain pipe Gas connection Liquid connection Airflow Air inlet from bottom side Air filter Airflow Fig.
INSTALLATION CLEARANCES > 11.8in(30cm) Strong and durable ceiling >0.8in(2cm) Indoor unit Right Left side side > 0.8in(2cm) Access Panel Ceiling opening size Service access Ceiling > > Ceiling opening size Floor Maintenance space Fig. 6 − Installation Clearances MAINTENANCE CLEARANCES Bottom Return Blower/Motor Service Clearance Service access...
INSTALLATION LOCATION REQUIREMENTS 5. Secure the unit in position with lock nuts and washers on Indoor Unit S Confirm that the ceiling is able to support the weight of the unit. both sides of the mounting bracket. Ensure the threaded S There should be enough room within the false ceiling for rod does not extend more than 2 in.
Page 9
INSTALLING DUCTWORK S Condensate piping must not be installed where it may be Connect the return and supply ducts to the duct collars provided on the unit. Adequate distance between the return and supply diffusers exposed to freezing temperatures. should be maintained to avoid short circulation of air within the space. S To prevent the pipe from sagging, space hanging wires every The filter is located on the return side of the unit, on the rear or 39−59in.
Page 10
(3.) Sizes 24, 36, 48 and 58 have a built−in condensate lift pump. CONDENSATE DRAIN AND CONDENSATE LIFT The drain connections (A, B and C) are covered with caps. PUMP INSTALLATION (HORIZONTAL a. Connect the drainpipe to connector D (see Fig. 21). INSTALLATION) For sizes 9, 12 and 18, the condensate lift pump has been provided in a separate box.
Page 11
Remove the cap from connector C and connect the condensate drain pipe to drain connector C. (see Fig. 25). NOTE: For size 18, the External Condensate lift pump should be removed (see Fig. 24). Connector C Fig. 24 − Sizes 9, 12, 18 with External Condensate Lift Pump Connector C Fig.
EXTERNAL STATIC PRESSURE Using the KSACN0501AAA Wired Controller, the external static CAUTION CAUTION pressure can: S Be manually changed to the fan curves SP2, SP3, SP4. S Choose the Automatic Airflow “AF” adjustment function which DAMPERS will automatically identify the static pressure and regulate the DO NOT adjust the dampers when the automatic airflow amount of airflow.
FAN PERFORMANCES AT VARYING STATIC PRESSURES Table 6 – Static Pressure at the Rated Point and Static Pressure Range Static Pressure at Rated Point Size Units Static Pressure Range In. WG 0.068 0.104 0.128 0.176 0~0.20 (0~50) In. WG 0.064 0.10 0.136 0.20...
Page 14
FAN PERFORMANCES AT VARYING STATIC PRESSURES (CONT) Fig. 32 − Fan Performance − 40MBDQ09...
Page 15
FAN PERFORMANCES AT VARYING STATIC PRESSURES (CONT) Fig. 33 − Fan Performance − 40MBDQ12...
Page 16
FAN PERFORMANCES AT VARYING STATIC PRESSURES (CONT) Fig. 34 − Fan Performance − 40MBDQ18...
Page 17
FAN PERFORMANCES AT VARYING STATIC PRESSURES (CONT) Fig. 35 − Fan Performance − 40MBDQ24...
Page 18
FAN PERFORMANCES AT VARYING STATIC PRESSURES (CONT) Fig. 36 − Fan Performance − 40MBDQ36...
Page 19
FAN PERFORMANCES AT VARYING STATIC PRESSURES (CONT) Fig. 37 − Fan Performance − 40MBDQ48...
Page 20
FAN PERFORMANCES AT VARYING STATIC PRESSURES (CONT) Fig. 38 − Fan Performance − 40MBDQ58...
ELECTRICAL DATA Table 8 – Electrical Data INDOOR FAN MAX FUSE CB AMP UNIT SIZE V-PH-HZ 1.11 0.18 1.11 0.18 0.27 Refer to outdoor unit installation instructions – Indoor unit powered by the outdoor unit 208-230/1/60 0.27 2.45 0.56 0.75 3.65 0.952 1000...
Page 22
INSTALL ALL POWER, INTERCONNECTING h. Apply a small amount of refrigerant oil to the flare connection on the tubing. WIRING, AND PIPING TO INDOOR UNIT i. Align center of the pipes and/or service valve. 1. Run interconnecting piping and wiring from the outdoor unit to the indoor unit.
Page 23
WIRELESS REMOTE CONTROL INSTALLATION Mounting Bracket (if installed on the wall) 1. Use the two screws supplied with control to attach the mounting bracket to the wall in a location selected by customer and within operating range. 2. Install batteries in the remote control. 3.
SYSTEM CHECKS CAUTION 1. Conceal the tubing where possible. 2. Ensure the drain tube slopes downward along its entire UNIT DAMAGE HAZARD length. Failure to follow this caution may result in equipment 3. Ensure all tubing and connections are properly insulated. damage or improper operation.
TROUBLESHOOTING For ease of service, the systems are equipped with diagnostic code The indoor diagnostic display is a combination of flashing LEDs display LEDs on both the indoor and outdoor units. The outdoor on the display panel or the front of the unit. If possible, always diagnostic display consists of two LEDs (Red and Green) on the check the diagnostic codes displayed on the indoor unit first.
Page 26
Catalog No: IM-40MBDQ-04 Copyright 2018 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 09/18 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: IM-40MBDQ-03...
Need help?
Do you have a question about the 40MBDQ09 3 Series and is the answer not in the manual?
Questions and answers