Second Environment (Drive Of Category C3); Second Environment (Drive Of Category C4); Marine Type Approvals - ABB ACS800 Hardware Manual

Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

Second environment (drive of category C3)

The drive complies with the standard with the following provisions:
1. Frame sizes R2...R5: The drive is equipped with EMC filter +E200. The filter is suitable for TN
(earthed) systems only.
Frame size R6: The drive is equipped with EMC filter +E210. The filter is suitable for TN (earthed)
and IT (unearthed) systems.
2. The motor and control cables are selected as specified in the Hardware Manual.
3. The drive is installed according to the instructions given in the Hardware Manual.
4. Maximum cable length is 100 metres.
WARNING! A drive of category C3 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.

Second environment (drive of category C4)

If the provisions under
be equipped with EMC filter +E200 when installed to an IT (unearthed) network, the requirements of the
standard can be met as follows for restricted distribution:
1. It is ensured that no excessive emission is propagated to neighbouring low-voltage networks. In
some cases, the inherent suppression in transformers and cables is sufficient. If in doubt, a supply
transformer with static screening between the primary and secondary windings can be used.
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available
from the local ABB representative.
3. The motor and control cables are selected as specified in the Hardware Manual.
4. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such a
network.

Marine type approvals

See ACS800-01/U1/04/U4 Marine Supplement [3AFE68291275 (English)].
Second environment (drive of category C3)
Medium voltage network
Neighbouring network
Point of measurement
Low voltage
Equipment
(victim)
Equipment
cannot be met, e.g. the drive cannot
Supply transformer
Static screen
Low voltage
Drive
Equipment
113
Technical data

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-01Acs800-u1

Table of Contents