Warning Sticker; Cabinet Installation (Ip 21, Ul Type 1) - ABB ACS800 Hardware Manual

Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

Wire size
MCM/AWG
6
4
2
1
1/0
2/0
8. Tighten the clamping nuts of the cable glands.
After connecting the control cables, fasten the front covers.

Warning sticker

There are warning stickers in different languages inside the packing box of the drive.
Attach a warning sticker in the language of your choice onto the plastic skeleton
above the power cable terminals.

Cabinet installation (IP 21, UL type 1)

The drive can be installed in a cabinet without the connection box and front cover.
It is recommended:
• to ground the cable shield 360 degrees at the cabinet entry
• to lead the cable unstripped as close to the terminals as possible.
Secure the cables mechanically.
Compression lug
Manufacturer
Burndy
YAV6C-L2
Ilsco
CCL-6-38
Burndy
YA4C-L4BOX
Ilsco
CCL-4-38
Burndy
YA2C-L4BOX
Ilsco
CRC-2
Ilsco
CCL-2-38
Burndy
YA1C-L4BOX
Ilsco
CRA-1-38
Ilsco
CCL-1-38
Thomas & Betts 54148
Burndy
YA25-L4BOX
Ilsco
CRB-0
Ilsco
CCL-1/0-38
Thomas & Betts 54109
Burndy
YAL26T38
Ilsco
CRA-2/0
Ilsco
CCL-2/0-38
Thomas & Betts 54110
Type
Manufacturer
Burndy
Ilsco
Burndy
Ilsco
Burndy
Ilsco
Ilsco
Burndy
Ilsco
Ilsco
Thomas & Betts
Burndy
Ilsco
Ilsco
Thomas & Betts
Burndy
Ilsco
Ilsco
Thomas & Betts
Crimping tool
Type
No. of crimps
MY29-3
1
ILC-10
2
MY29-3
1
MT-25
1
MY29-3
2
IDT-12
1
MT-25
1
MY29-3
2
IDT-12
1
MT-25
1
TBM-8
3
MY29-3
2
IDT-12
1
MT-25
1
TBM-8
3
MY29-3
2
IDT-12
1
MT-25
1
TBM-8
3
Electrical installation