Do you have a question about the EKC 202D and is the answer not in the manual?
Questions and answers
Leopold Makambila
January 16, 2025
Is there a possibility with the EKC 202D2 to correct the temperature sensor reading offset,
1 comments:
Mr. Anderson
February 3, 2025
Yes, the Danfoss EKC 202D can correct the temperature sensor reading offset. This is done using the parameters r09 and r10, which allow for the correction of the signal from sensors S4 and S3, respectively. Both parameters have a correction range of -10.0 K to 10.0 K.
Need help?
Do you have a question about the EKC 202D and is the answer not in the manual?
Questions and answers
Is there a possibility with the EKC 202D2 to correct the temperature sensor reading offset,
Yes, the Danfoss EKC 202D can correct the temperature sensor reading offset. This is done using the parameters r09 and r10, which allow for the correction of the signal from sensors S4 and S3, respectively. Both parameters have a correction range of -10.0 K to 10.0 K.