Connecting
4.1 Additional rules and provisions for operation of the ET 200SP with fail-safe modules
Power supply requirements for compliance with NAMUR recommendations
Note
To ensure adherence to the NAMUR recommendation NE 21, IEC 61131-2 and EN 298,
only use power packs/power supply units (230 V AC → 24 V DC) with a mains buffering time
of at least 20 ms. The latest up-to-date information on PS components is available on the
Internet (http://mall.automation.siemens.com).
It goes without saying that these requirements also apply to power packs/power supply units
not constructed using ET 200SP / S7-300/-400/-1500 technology.
4.1.2
Requirements of sensors and actuators for fail-safe modules
General requirements for sensors and actuators
Note the following important warning regarding safety-related use of sensors and actuators:
Note that instrumentation with sensors and actuators bears a considerable safety
responsibility. Also bear in mind that sensors and actuators generally do not have proof-test
intervals of 20 years as defined in IEC 61508:2010 without considerable loss of safety.
The probability of hazardous faults and the rate of hazardous faults of safety functions must
comply with an SIL-defined high limit. A listing of values achieved by F-modules in the
technical specifications of the F-modules is available under "Fail-safe performance
characteristics".
To achieve the respective safety class, suitably qualified sensors and actuators are
necessary.
18
WARNING
ET 200SP distributed I/O system
Product Information, 07/2013, A5E32288220-AA