6.2 Brief Description of Modes and Functions

1. Temperature Parameters
◆ Indoor preset temperature (T
◆ Indoor ambient temperature (T
2. Basic Functions
Once energized, in no case should the compressor be restarted within less than 3 minutes. In the situation that memory function is
available, for the first energization, if the compressor is at stop before de-energization, the compressor will be started without a 3-minute
lag; if the compressor is in operation before de-energization, the compressor will be started with a 3-minute lag; and once started, the
compressor will not be stopped within 6 minutes regardless of changes in room temperature;
(1)COOL Mode
① The condition and process of cooling
If T
≥T
COOL mode will act, the compressor and outdoor fan will run, and the indoor fan will run at the set speed.
amb.
preset
If T
.≤T
-2°C,the compressor will stop, the outdoor fan will delay 30 seconds to stop, and the indoor fan will run at the set speed.
amb
preset
If T
-2°C≤T
≤T
preset
amb.
preset
In this mode, the reversal valve will not be powered on and the temperature setting range is 16~30°C.
② Protection function
◆ Overcurrent protection
If total current is high, the compressor will run in limited frequency. If total current is too high, the compressor will stop, the outdoor fan
will delay 30 seconds to stop, indoor unit will display E5 and outdoor yellow light will blink 5 times.
◆ Antifreezing protection
When the antifreezing protection is detected, the compressor will stop, the outdoor fan will stop after 30 seconds, and the indoor fan and
swing motor will keep running in the original mode. When antifreezing protection is eliminated and the compressor has stopped for 3
minutes, the compressor will resume running in the original mode.
(2)Dehumidifying Mode
① Working conditions and process of dehumidifying
If T
>T
the unit will enter cooling and dehumidifying mode, in which case the compressor and the outdoor fan will operate and the
amb.
preset,
indoor fan will run at low speed.
If T
-2°C≤T
≤T
preset
amb.
preset
If T
<T
-2°C, the compressor will stop, the outdoor fan will stop with a time lag of 30s, and the indoor fan will operate at low speed.
amb.
preset
② Protection
Protection is the same as that under the cooling mode.
(3) HEAT Mode
① The condition and process of heating
If T
≤T
+2°C , HEAT mode will act, the compressor, outdoor fan and reversal valve will run, the indoor fan will delay 3min to stop at
amb
preset
the latest.
If T
+2°C<T
< T
preset
amb
preset
If T
≥T
+5°C , the compressor will stop, the outdoor fan will delay 30sec to stop and indoor fan will blow 60S at low speed, the fan
amb.
preset
speed cannot be shifted within blow residual heat.
◆ In this mode, the temperature setting range is 16~30°C.
◆ The air conditioner will adjust the running frequency of the compressor automatically according to the change of ambient temperature.
◆ When the unit is turned off in HEAT mode, or switched to other mode from HEAT mode, the four-way valve will be powered off after
16
)
preset
)
amb.
,the unit will keep running in the previous mode.
Tamb.
Tpreset
Tamb.
Tpreset
Tpreset –2 ˚C
Tpreset –2 ˚C
≥ 6 min.
≥ 6 min.
Compressor
Compressor
Outdoor fan
Outdoor fan
Indoor fan
Indoor fan
Compressor
Outdoor fan
Compressor
Indoor fan
Outdoor fan
Indoor fan
, the compressor remains at its original operation state.
+5°C ,the unit will keep running in the original mode.
≥ 3 min.
≥ 6 min.
≥ 3 min.
≥ 6 min.
Setting fan speed
Setting fan speed
Run
Stop
Run
Stop
During antifreeze protection
min
During antifreeze protection
min
Preset speed
Run
Stop
Preset speed
Run
Stop
Start cooling
Original operating status
Start cooling
Original operating status
Stop cooling
Stop cooling
Service Manual