Models: GWH09YC-K6DNA1A
GWH09YC-K6DNA2A
GWH12YC-K6DNA1A
GWH12YC-K6DNA2A
(Refrigerant R32)
GREE ELECTRIC APPLIANCES,INC.OF ZHUHAI

Advertisement

Table of Contents
loading

Summary of Contents for Gree GWH09YC-K6DNA1A

  • Page 1 Change for Life Service Manual Models: GWH09YC-K6DNA1A GWH09YC-K6DNA2A GWH12YC-K6DNA1A GWH12YC-K6DNA2A (Refrigerant R32) GREE ELECTRIC APPLIANCES,INC.OF ZHUHAI...
  • Page 2: Table Of Contents

    5.2 PCB Printed Diagram .....................16 6. Function and Control ..................18 6.1 Remote Controller Introduction ..................18 6.2 GREE+ App Operation Manual ..................23 6.3 Ewpe Smart App Operation Manual ................24 6.4 Brief Description of Modes and Functions ..............25 Part Ⅱ : Installation and Maintenance ..........30...
  • Page 3 Service Manual 9. Maintenance ......................40 9.1 Troubleshooting for Normal Malfunction .................40 9.2 Error Code List .......................44 9.3 Troubleshooting for Main Malfunction ................51 10. Exploded View and Parts List ..............63 10.1 Indoor Unit ........................63 10.2 Outdoor Unit .........................67 11. Removal Procedure ..................70 11.1 Removal Procedure of Indoor Unit ................70 11.2 Removal Procedure of Outdoor Unit ................75...
  • Page 4: Part Ⅰ : Technical Information

    Service Manual Part Ⅰ : Technical Information 1. Summary Indoor Unit GWH09YC-K6DNA1A/I GWH12YC-K6DNA1A/I GWH09YC-K6DNA2A/I GWH12YC-K6DNA2A/I Outdoor Unit GWH09YC-K6DNA1A/O GWH12YC-K6DNA1A/O Remote Controller YAG1FB MODE ON/OFF Technical Information...
  • Page 5: Specifications

    Service Manual 2. Specifications 2.1 Specification Sheet Parameter Unit Value GWH09YC-K6DNA1A GWH12YC-K6DNA1A Model GWH09YC-K6DNA2A GWH12YC-K6DNA2A CB437001600 CB437001100 Product Code CB466001600 CB466001500 Rated Voltage 220-240 220-240 Power Rated Frequency Supply Phases Power Supply Mode Outdoor Outdoor Cooling Capacity 2700 3500 Heating Capacity...
  • Page 6 Service Manual Outdoor Unit Model GWH09YC-K6DNA1A/O GWH12YC-K6DNA1A/O Outdoor Unit Product Code CB437W01600 CB437W01100 ZHUHAI LANDA COMPRESSOR ZHUHAI LANDA COMPRESSOR Compressor Manufacturer CO.,LTD CO., LTD Compressor Model QXF-B096zE190A QXF-B096zE190A Compressor Oil FW68DA FW68DA Compressor Type Rotary Rotary Compressor LRA. 20.00 Compressor RLA 4.21...
  • Page 7 Service Manual Parameter Unit Value GWH12YC-K6DNA1A GWH09YC-K6DNA1A Model GWH12YC-K6DNA2A GWH09YC-K6DNA2A CB437001101 CB437001601 Product Code CB466001501 CB466001601 Rated Voltage 220-240 220-240 Power Rated Frequency Supply Phases Power Supply Mode Outdoor Outdoor Cooling Capacity 3500 2700 Heating Capacity 3810 2930 Cooling Power Input...
  • Page 8 Service Manual Outdoor Unit Model GWH12YC-K6DNA1A/O GWH09YC-K6DNA1A/O(LCLH) Outdoor Unit Product Code CB437W01101 CB437W01601 ZHUHAI LANDA COMPRESSOR ZHUHAI LANDA COMPRESSOR Compressor Manufacturer CO., LTD CO.,LTD Compressor Model QXF-B096zE190A QXF-B096zE190A Compressor Oil FW68DA FW68DA Compressor Type Rotary Rotary Compressor LRA. 20.00 Compressor RLA 4.21...
  • Page 9: Operation Characteristic Curve

    Indoor air flow:Turbo Indoor:DB 27 WB19 Pipe length:5m Indoor air flow: Turbo Voltage:230V Pipe length:5m Voltage:230V Compressor Speed(rps) Compressor Speed(rps) 2.3 Capacity Variation Ratio According to Temperature GWH09YC-K6DNA1A/O GWH12YC-K6DNA1A/O Cooling: Heating: Condition Condition Indoor:DB20℃ Indoor:DB27℃ WB19℃ Condition Indoor air flow: Condition...
  • Page 10 Service Manual GWH12YC-K6DNA1A/O GWH09YC-K6DNA1A/O GWH09YC-K6DNA1A/O Cooling: Heating: Condition Condition Indoor:DB 20°C WB19 °C Indoor:DB 27°C Indoor air flow: Super High Indoor air flow: Super High Pipe length:5m Pipe length:5m Outdoor temp. (°C) Outdoor temp. (°C) Cooling Heating Conditions Conditions Indoor:DB27°C/WB19°C Indoor:DB20°C/WB15°C...
  • Page 11: Cooling And Heating Data Sheet In Rated Frequency

    Service Manual 2.4 Cooling and Heating Data Sheet in Rated Frequency Cooling: Pressure of gas pipe Inlet and outlet pipe Rated cooling Compressor connecting indoor and temperature of heat Fan speed of Fan speed of condition(°C) (DB/WB) Model revolution outdoor unit exchanger indoor unit outdoor unit...
  • Page 12: Outline Dimension Diagram

    Service Manual 3. Outline Dimension Diagram 3.1 Indoor Unit 133.5 541.6 189.9 Φ55 Φ55 Unit:mm 124.7 83.2 Technical Information...
  • Page 13: Outdoor Unit

    Service Manual 3.2 Outdoor Unit Unit:mm Technical Information...
  • Page 14: Refrigerant System Diagram

    Service Manual 4. Refrigerant System Diagram Indoor unit Outdoor unit Gas pipe side Valve 4-Way valve Di s charge Heat Accumlator Suction exchanger Compressor (evaporator) Heat exchanger Liquid pipe (condenser) side Valve Strainer Capillary Electron Strainer expansion valve COOLING HEATING Connection pipe specification: Liquid pipe:1/4"...
  • Page 15: Electrical Part

    Brown COMP Compressor Blue Grounding wire YEGN Yellow/Green Black Violet Orange Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model. ● Indoor Unit GWH09YC-K6DNA1A/I(CB437N01600) GWH12YC-K6DNA1A/I(CB437N01100) GWH12YC-K6DNA2A/I GWH09YC-K6DNA2A/I 60000700030904 Technical Information...
  • Page 16 Service Manual GWH12YC-K6DNA1A/I(CB437N01101) GWH09YC-K6DNA1A/I(CB437N01601) 60000700030902 Technical Information...
  • Page 17 Service Manual ● Outdoor Unit GWH09YC-K6DNA1A/O(CB437W01600) GWH12YC-K6DNA1A/O(CB437W01100) 6361000008401 GWH12YC-K6DNA1A/O(CB437W01101) 600007001110 Technical Information...
  • Page 18 Service Manual GWH09YC-K6DNA1A/O(CB437W01601) WARNING OUTTUBE OUTROOM EXHAUST ELECTRONIC REACTOR Please don't touch any TEMP. TEMP. TEMP. EXPANSION 4-WAY terminal when the machine is SENSOR SENSOR SENSOR VALVE VALVE running ,stopping or has been powered off for less than 30 minutes to prevent the risk...
  • Page 19: Pcb Printed Diagram

    Service Manual 5.2 PCB Printed Diagram Indoor Unit ● Top view Name Neutral wire Needle stand for indoor fan Auto button Up&down swing motor left&right swing motor Interface of temperature sensor Terminal for display board connection Terminal of jumper cap Communication wire Connect earthing wire(only for the mode with this function)
  • Page 20 Service Manual Outdoor Unit ● Top view Name Compressor Reactor 2 Reactor 1 Chassis electric heating Compressor electric heating 4-way valve DC fan Earthing wire Communication wire Neutral wire Live wire Electronic expansion valve Temperature sensor Overloard Dred ● Bottom view Technical Information...
  • Page 21: Function And Control

    Service Manual 6. Function and Control 6.1 Remote Controller Introduction Buttons on Remote Controller ON/OFF button FAN button MODE button +/- button TURBO button button button CLOCK button TIMER ON/ TIMER OFF button TEMP button button (before opening cover (after opening cover I FEEL button ON/OFF button LIGHT button...
  • Page 22 Service Manual 2. FAN button Press this button, Auto, Low, Medium-low, Medium, Medium-high, High speed can be circularly selected. After powered on, Auto fan speed is default. Under DRY mode, Low fan speed only can be set up. ATUO Note: It’s Low fan speed under Dry mode.
  • Page 23 Service Manual TIMER ON. 10. TEMP button Press this button,the following temperature can be setted circularly: the setting temperature, indoor ambient temperature and outdoor ,displaying the indoor ambient temperature. is the outdoor ambient temperature. 3s laterit will return to the setting temprature or it depends on the other received signal within3s.
  • Page 24 Service Manual the place of setting temperature "88" will display the corresponding temperature of last setting sleep curve and blink; control will resume the original timer display;temperature display will resume to original setting temperature. Sleep3- the sleep curve setting under Sleep mode by DIY could be inquired: The user could accord to sleep curve setting method to inquire the presetting sleep curve, enter into user individuation sleep setting status, Note: In the above presetting or enquiry procedure, if continuously within10s, there is no button pressed, the sleep curve setting status will be automatically quit and resume to display the original displaying.
  • Page 25 Service Manual Operation Guide 1. General operation (1)After powered on, press ON/OFF button, the unit will start to run. (Note: When it is powered on, the guide louver of main unit will close automatically.) (2)Press MODE button, select desired running mode. (3)Pressing + or - button, to set the desired temperature (It is unnecessary to set the temp.
  • Page 26: Gree+ App Operation Manual

    GREE+ App Download Linkage Scan the QR code or search "GREE+" in the application market to download and install it. When "GREE+" App is installed, register the account and add the device to achieve long-distance control and LAN control of Gree smart home appliances.
  • Page 27: Ewpe Smart App Operation Manual

    Service Manual 6.3 Ewpe Smart App Operation Manual Control Flow Chart Internet Cloud intelligent Home Wi-Fi Cellular/ home Other Wi-FI appliances Home wireless router Home Wi-Fi Operating Systems Requirement for User's smart phone: iOS system Android system Support iOS7.0 and Support Android 4.0 and above version above version...
  • Page 28: Brief Description Of Modes And Functions

    Service Manual 6.4 Brief Description of Modes and Functions 1. Temperature Parameters ◆ Indoor preset temperature (T preset ◆ Indoor ambient temperature (T amb. 2. Basic Functions Once energized, in no case should the compressor be restarted within less than 3 minutes. In the situation that memory function is avail- able, for the first energization, if the compressor is at stop before de-energization, the compressor will be started without a 3-minute lag;...
  • Page 29 Service Manual ◆ When compressor is running (not including each malfunction and protection): a.When outdoor ambient temperature≥20°C and indoor fan speed is low or medium, the fan speed will turn to high; if indoor fan speed is high or super high, it will keep the same. b.When outdoor ambient temperature≤18°C, the fan speed will resume set fan speed.
  • Page 30 Service Manual c.For heating and cooling unit, when 22°C<Tindoor ambient<26°C (for cooling only unit, 22°C<Tindoor ambient<26°C), it will keep the original running mode. If the unit is energized for the first time, it will run in fan mode. ② Protection a.
  • Page 31 Service Manual 1. In cooling mode: 1.1 When the initial set temperature is16-23°C,the temperature will rise 1°C by every hour after sleep function is set;the temperature will not change after rising 3°C;after running for 7hours,the temperature will decrease1°C and it will not change after that. 1.2 When the initial set temperature is 24-27°C,the temperature will rise 1°C by every hour after sleep function is set;...
  • Page 32 Service Manual 1. Under heating mode: auto speed under heating or auto heating mode: a. When T ≤T +1°C, indoor fan will operate at high speed; amb. preset b. When T +1°C<T <T +3°C, indoor fan will operate at medium speed; preset amb.
  • Page 33: Part Ⅱ : Installation And Maintenance

    Service Manual Part : Installation and Maintenance Ⅱ 7. Notes for Installation and Maintenance Safety Precautions: 10. If the power cord or connection wire is not long enough, please get the specialized power cord or connection wire Important! from the manufacture or distributor. Prohibit prolong the wire by yourself.
  • Page 34 Service Manual Safety Operation of Flammable Refrigerant Qualification requirement for installation and maintenance man ●All the work men who are engaging in the refrigeration system should bear the valid certification awarded by the authoritative organization and the qualification for dealing with the refrigeration system recognized by this industry. If it needs other technician to maintain and repair the appliance, they should be supervised by the person who bears the qualification for using the flammable refrigerant.
  • Page 35 Service Manual Main Tools for Installation and Maintenance 1. Level meter, measuring tape 2. Screw driver 3. Impact drill, drill head, electric drill 4. Electroprobe 5. Universal meter 6. Torque wrench, open-end wrench, inner hexagon spanner 7. Electronic leakage detector 8.
  • Page 36: Installation

    Service Manual 8. Installation 8.1 Installation Dimension Diagram Space to the wall At least 15cm At least 15cm Space to the wall Drainage pipe Installation and Maintenance...
  • Page 37 Service Manual Start installation Preparation before installation Read the requirements select installation Prepare tools for electric connection location Select indoor unit Select outdoor unit installation location installation location Install the support of outdoor unit Install wall-mounting (select it according to the actual situation) frame, drill wall holes Connect pipes of indoor Fix outdoor unit...
  • Page 38: Installation Parts-Checking

    Service Manual 8.4 Requirements for electric connection 8.2 Installation Parts-checking 1. Safety Precaution Name Name (1) Must follow the electric safety regulations when installing Indoor unit Sealing gum the unit. Outdoor unit Wrapping tape (2) According to the local safety regulations, use qualified Support of outdoor power supply circuit and air switch.
  • Page 39 Service Manual screw fixing holes on the wall. 5. Connect the Pipe of Indoor Unit (2) Drill the screw fixing holes on the wall with impact drill (the (1) Aim the pipe joint at the corresponding bellmouth.(As show specification of drill head should be the same as the plastic in Fig.5) expansion particle) and then fill the plastic expansion particles (2) Pretightening the union nut with hand.
  • Page 40 Service Manual 7. Connect Wire of Indoor Unit 8. Bind up Pipe (1) Open the panel, remove the screw on the wiring cover and (1) Bind up the connection pipe, power cord and drain hose then take down the cover.(As show in Fig.11) with the band.(As show in Fig.14) (2) Reserve a certain length of drain hose and power cord Screw...
  • Page 41: Installation Of Outdoor Unit

    Service Manual 8.6 Installation of Outdoor Unit (3) Pretightening the union nut with hand. (4) Tighten the union nut with torque wrench . 1. Fix the Support of Outdoor Unit(Select it according to the actual installation situation) Refer to the following table for wrench moment of force: (1) Select installation location according to the house structure.
  • Page 42: Vacuum Pumping And Leak Detection

    Service Manual Note: 2. Leakage Detection (1) With leakage detector: (1) The through-wall height of drain hose shouldn't be higher Check if there is leakage with leakage detector. than the outlet pipe hole of indoor unit.(As show in Fig.25) (2) With soap water: (2) Slant the drain hose slightly downwards.
  • Page 43: Maintenance

    Service Manual 9. Maintenance 9.1 Troubleshooting for Normal Malfunction Note: When replacing the controller, make sure insert the wire jumper into the new controller, otherwise the unit will display C5. Measure insulation resistance The breaker trips at once when it to ground to see if there is any is set to “ON”.
  • Page 44 Service Manual Improper set of temperature Adjust set temperature If cooling (heating) load is Check the forecasted load of cooling (heating) proper Check and fill the leakage, then The refrigerant has leakage or is vacuumize it and supplement the re- insufficient frigerant as required Leakage between the high pres-...
  • Page 45 Service Manual The indoor fan motor is burned or breaks or has the heat protector Replace the fan motor or the defective part. malfunction. The built-in heat protector of the Replace the fan motor The fan does not motor breaks frequently because the run when it is set motor is abnormal.
  • Page 46 Service Manual The torque of the swing motor is not enough First, check whether the connection is Wrong connection The swing fan wrong. If no, replace the parts does not run. The controller is damaged(IC2003 is damaged, the swing relay can not close, etc) C o n t r o l l e r m a l f u n c t i o n ( I C 2 0 0 3 Change controller...
  • Page 47: Error Code List

    Service Manual 9.2 Error Code List Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s) Code...
  • Page 48 Service Manual Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s) Code...
  • Page 49 Service Manual Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s) Code...
  • Page 50 Service Manual Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s) Code...
  • Page 51 Service Manual Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s) Code...
  • Page 52 Service Manual Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s) Code...
  • Page 53 Service Manual Display Method of Indoor Unit Display Method of Outdoor Unit Indicator Display (during Indicator has 3 kinds of display blinking, ON 0.5s and OFF status and during blinking, ON Dual-8 Malfunction A/C status Possible Causes 0.5s) 0.5s and OFF 0.5s Code Name Operation...
  • Page 54: Troubleshooting For Main Malfunction

    Service Manual 9.3 Troubleshooting for Main Malfunction Indoor unit 1. Malfunction of Temperature Sensor F1, F2 Main detection points: ● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted? ● Is there short circuit due to trip-over of the parts? ●...
  • Page 55 Service Manual 2. Malfunction of Blocked Protection of IDU Fan Motor H6 Malfunction diagnosis process: Start Turn the fan blades by hand under power-off condition Adjust the motor and blade Whether the fan blades assembly so that rotor can run can run smoothly? smoothly.
  • Page 56 Service Manual 3. Malfunction of detecting plate(WIFI) JF 5. Malfunction of detecting plate(WIFI) JF Start check if the connection wire are correctly connected detecting Replace the plate with the same model Is malfunction eliminated Replace the mainboard with the same model The end Installation and Maintenance...
  • Page 57 Service Manual 4. Malfunction of Protection of Jumper Cap C5 Main detection points: ● Is there jumper cap on the mainboard? ● Is the jumper cap inserted correctly and tightly? ● The jumper is broken? ● The motor is broken? ●...
  • Page 58 Service Manual Outdoor unit (1) Capacitor charge fault (Fault with outdoor unit) (AP1 below refers to the outdoor control panel) Main Check Points: ●Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC~240VAC. ●Is the reactor (L) correctly connected? Is the connection loose or fallen? Is the reactor (L) damaged? Fault diagnosis process: Turn on the unit...
  • Page 59 Service Manual (2) IPM Protection, Out-of-step Fault, Compressor Phase Overcurrent (AP1 below refers to the outdoor control panel) Main check points: ●Is the connection between control panel AP1 and compressor COMP secure? Loose? Is the connection in correct order? ●Is the voltage input of the machine within normal range? (Use AC voltmeter to measure the voltage between terminal L and N on the wiring board XT) ●Is the compressor coil resistance normal? Is the insulation of compressor coil against the copper tube in good condition? ●Is the working load of the machine too high? Is the radiation good?
  • Page 60 Service Manual (3)High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the outdoor unit) Mainly detect: ●Is outdoor ambient temperature in normal range? ●Are the outdoor and indoor fans operating normally? ●Is the heat dissipation environment inside and outside the unit good? Fault diagnosis process: Overheat and high temperature protection...
  • Page 61 Service Manual (4) Start-up failure (following AP1 for outdoor unit control board) Mainly detect: ●Whether the compressor wiring is connected correct? ●Is compressor broken? ●Is time for compressor stopping enough? Fault diagnosis process: Power on the unit Restart it up after Is stop time of the compressor 3 minutes longer than 3 minutes?
  • Page 62 Service Manual (5) Out of step diagnosis for the compressor (AP1 hereinafter refers to the control board of the outdoor unit) Mainly detect: ●Is the system pressure too high? ●Is the input voltage too low? Fault diagnosis process: Out of step occurs in Out of step occurs once the operation unit is powered on.
  • Page 63 Service Manual (6)Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board) Mainly detect: ●Is the PMV connected well or not? Is PMV damaged? ●Is refrigerant leaked? Fault diagnosis process: 20 minutes after the complete unit is powered off Is the terminal FA for the Connect the...
  • Page 64 Service Manual (7)Power factor correct or (PFC) fault (a fault of outdoor unit) (AP1 hereinafter refers to the control board of the outdoor unit) Mainly detect: ●Check if the reactor (L) of the outdoor unit and the PFC capacitor are broken Fault diagnosis process: Start Check wiring of the...
  • Page 65 Service Manual (8) Communication malfunction: (following AP1 for outdoor unit control board) Mainly detect: ●Is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged? ●Detect the indoor and outdoor units connection wire and indoor and outdoor units inside wiring is connect well or not, if is there any damage? Fault diagnosis process: Start...
  • Page 66: Exploded View And Parts List

    Service Manual 10. Exploded View and Parts List 10.1 Indoor Unit MODE ON/OFF The component picture is only for reference; please refer to the actual product. Installation and Maintenance...
  • Page 67 Service Manual Part Code Description GWH09YC-K6DNA1A/I GWH12YC-K6DNA1A/I GWH12YC-K6DNA1A/I Product Code CB437N01600 CB437N01100 CB437N01101 Front Panel 20000300055T 20000300055T 20000300055T Filter Sub-Assy 11122468 11122468 11122468 Screw Cover 2425203001 2425203001 2425203001 Front Case Assy 00000200067 00000200067 00000200067 Guide Louver 10512338 10512338 10512338 Helicoid Tongue...
  • Page 68 Service Manual Part Code Description GWH09YC-K6DNA1A/I GWH12YC-K6DNA2A/I GWH09YC-K6DNA2A/I Product Code CB437N01601 CB466N01500 CB466N01600 Front Panel 20000300055T 200003000077 200003000077 Filter Sub-Assy 11122468 11122468 11122468 Screw Cover 2425203001 2425203001 2425203001 Front Case Assy 00000200067 00000200067 00000200067 Guide Louver 10512338 10512338 10512338 Helicoid Tongue...
  • Page 69 Service Manual Part Code Description GWH09YC-K6DNA2A/I GWH12YC-K6DNA2A/I Product Code CB466N01601 CB466N01501 Front Panel 200003000077 200003000077 Filter Sub-Assy 11122468 11122468 Screw Cover 2425203001 2425203001 Front Case Assy 00000200067 00000200067 Guide Louver 10512338 10512338 Helicoid Tongue 26112436 26112436 Left Axile Bush 10512037 10512037 Rear Case assy 00000100179...
  • Page 70: Outdoor Unit

    Service Manual 10.2 Outdoor Unit 21 22 23 24 25 The component picture is only for reference; please refer to the actual product. Installation and Maintenance...
  • Page 71 Service Manual Part Code Description GWH09YC-K6DNA1A/O GWH12YC-K6DNA1A/O GWH12YC-K6DNA1A/O Product Code CB437W01600 CB437W01100 CB437W01101 Left Side Plate 01303200P 01303200P 01303200P Fan Motor 1501308507 1501308511 1501308507 Motor Support 01703136 01703136 01703136 Condenser Assy 011002000239 011002000245 011002000245 Top Cover Sub-Assy 01253081 01253081 01253081...
  • Page 72 Service Manual Part Code Description GWH09YC-K6DNA1A/O Product Code CB437W01601 Left Side Plate 01303200P Fan Motor 1501308507 Motor Support 01703136 Condenser Assy 011002000266 Top Cover Sub-Assy 01253081 Rear Grill 01475014 Clapboard Sub-Assy 01233180 Compressor and Fittings 00103925G Compressor Gasket 76710287 4-Way Valve Assy...
  • Page 73: Removal Procedure

    Service Manual 11. Removal Procedure Caution: discharge the refrigerant completely before removal. 11.1 Removal Procedure of Indoor Unit Step Procedure 1.Remove filter Panel Open the panel. Loosen the clasp shown and then pull the left filter and right filer outwards to remove them. Left filter and right filer 2.Remove horizontal louver Push out the axile bush on horizontal...
  • Page 74 Service Manual Step Procedure 3.Remove display and panel Screws Screws that are locking the display board. Display Separate the display board from the front Panel panel. Open the front panel; separate the panel rotation shaft from the groove fixing the front panel and then removes the front panel.
  • Page 75 Service Manual Step Procedure 7.Remove cold plasma generator Cold plasma generator Screws that are locking the cold plasma Screw generator.Separate the display board from the evaporator assy. 8.Remove temperature sensor and grounding wire Temperature sensor Grounding wire Cut off the tieline which binding the temperature sensor and grounding wire on the evaporator, and then pull out the indoor tube temperature sensor from the...
  • Page 76 Service Manual Step Procedure 11.Electric box assy Remove the screw fixing electric box assy and then remove the electric box assy. Electric box assy Screw 12.Remove connection pipe clamp Screw Connection pipe clamp At the back of the unit, remove the screw fixing connection pipe clamp and then remove the connection pipe clamp.
  • Page 77 Service Manual Step Procedure 15.Remove motor and cross flow blade Motor clamp Remove the screws fixing motor clamp Screws and then remove the motor clamp. Remove the screws at the connection place of cross flow blade and motor; lift the motor and cross flow blade upwards to remove them.
  • Page 78: Removal Procedure Of Outdoor Unit

    Service Manual 11.2 Removal Procedure of Outdoor Unit Steps Procedure 1.Remove big handle Before disassamble. Remove the screws fixing handle、valve big handle cover and then remove them. valve cover 2. Remove top cover top cover Remove the screws fixing top panel and then remove the top panel.
  • Page 79 Service Manual Step Procedure 3.Remove grille 、protective grille and front panel Remove connection screws between the front grille and the front panel. Then remove the front grille. Remove connection screws connecting the front protective panel with the chassis and the motor support, and grille then remove the front panel.
  • Page 80 Service Manual Step Procedure 6.Remove motor and motor support Remove the screws fixing motor and then remove the motor. Remove the screws fixing motor support and then remove the motor support. motor support motor 7.Remove electric box assy Remove the screws fixing electric box assy; cut off electric box assy the tieline;...
  • Page 81 Service Manual Step Procedure 9.Remove 4-way valve assy 4-way valve assy Unsolder the welding joints connecting the 4-way valve assy with capillary sub-assy, compressor and condenser; remove the 4-way valve.单冷机移除的为 吸排气管。 Note: Before unsoldering the welding joint, wrap the 4-way valve with a wet cloth completely to avoid damage to the valve caused by high temperature.
  • Page 82: Appendix

    Service Manual Appendix: Appendix 1: Reference Sheet of Celsius and Fahrenheit Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32 Set temperature Fahrenheit Fahrenheit Fahrenheit display Fahrenheit display Fahrenheit display Fahrenheit Celsius (℃) Celsius (℃) Celsius (℃) temperature temperature temperature (℉)...
  • Page 83: Appendix 3: Pipe Expanding Method

    Service Manual Appendix 3: Pipe Expanding Method Pipe Note: Pipe cutter Improper pipe expanding is the main cause of refrigerant leakage.Please expand the pipe according to the following steps: Leaning Uneven Burr A:Cut the pip ● Confirm the pipe length according to the distance of indoor unit and outdoor unit. ●...
  • Page 84: Appendix 4: List Of Resistance For Temperature Sensor

    Service Manual Appendix 4: List of Resistance for Temperature Sensor Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor (15K) Temp( C) Resistance(kΩ) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) Temp( Resistance(kΩ) 138.1 18.75 3.848 1.071 128.6 17.93 3.711 1.039 121.6 17.14 3.579 1.009...
  • Page 85 Service Manual Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K) Temp( C) Resistance(kΩ) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) Temp( Resistance(kΩ) 181.4 25.01 5.13 1.427 171.4 23.9 4.948 1.386 162.1 22.85 4.773 1.346 153.3 21.85 4.605 1.307 20.9 4.443 1.269 137.2...
  • Page 86 Service Manual Resistance Table of Discharge Temperature Sensor for Outdoor (50K) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) 853.5 18.34 4.75 799.8 93.42 17.65 4.61 89.07 16.99 4.47 703.8 84.95 16.36 4.33 660.8 81.05 15.75 4.20 620.8 77.35 15.17 4.08...
  • Page 87 GREE ELECTRIC APPLIANCES,INC.OF ZHUHAI Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China 519070 Tel: (+86-756) 8522218 Fax: (+86-756) 8669426 Email: gree@gree.com.cn Http://www.gree.com HONG KONG GREE ELECTRIC APPLIANCES SALES LIMITED Add: Unit 2612,26/F.,Miramar Tower 132 Nathan Road,TST,Kowloon,HK Tel: (852) 31658898 Fax: (852) 31651029...