Omron C200H Operation Manual page 56

Analog i/o units
Hide thumbs Also See for C200H:
Table of Contents

Advertisement

Specifications
Input Specifications
Converted output data
(Top: Binary
Parentheses: BCD)
0000
(8001)
(–0001)
87D0
(A000)
(–2000)
Note 1. The input signal range (0 to +10 V, +1 to +5 V/+4 to +20 mA, or –10 to +10 V) can be selected for each
input number. Refer to 2-3 Functions and Programming for details on setting the input signal range.
2. If an analog signal is input that exceeds the input signal range (max. value of +10 V or +5 V/20 mA, or
min. value of 0 V, +1 V/+4 mA, or –10 V), the digital output will remain fixed at the maximum or minimum
value.
3. When the input range is set to – 10 V to +10 V, the most significant bit (15
4. When the input range is set to – 10 V to +10 V and the analog input signal is 0 V, the digital output will be
"0000" and the most significant bit (15
48
0FA0
(4000)
0 to 10 V
1 to 5 V/4 to 20 mA
–10 to +10 V
07D0
(2000)
8FA0
10 V
–5 V
"1"
th
0 V 1 V
(4 mA)
th
Sign bit (15
bit)
bit) will be 0.
Appendix B
5 V
10 V
(20 mA)
Input signal
"0"
th
bit) becomes the sign bit.