Functions and Programming
Example 1
Example 2
24
Note
1. The resolution is fixed at 1/4000 if the (upper limit – lower limit) term is great-
er than 4000.
2. The resolution will be lower if the (upper limit – lower limit) term is less than
4000. For example, the resolution will be 1/2000 if the upper limit – lower
limit = 2000.
3. The scaling calculation won't be performed if the DM words don't contain
BCD data or the upper-limit data x lower-limit data.
4. When the scaling function is executed, the conversion data type setting is
ignored and the scaled data is output.
Input signal range: 0 to +10 V
Lower limit: 1000
Upper limit: 9000
Input signal range: –10 to +10 V
Lower limit: 1000
Upper limit: 7000
–10 V
Scaled data
Normal data
0 V
+5 V
Input signal
Scaled data
Normal data converted to the 0000 to 4000 range
(normal data + 2000).
–2 V
0 V
Input signal
Section 2-3
+10 V
+10 V