3| Areas of application

3.4 N and K versions

Models available:
• FKX50/460 N
• FKX50/555 N
• FKX50/460 K
• FKX50/555 K
• FKX50/830 N
• FKX50/980 N
• FKX50/830 K
• FKX50/980 K
3.4.1 Limits of application R134a (N and K versions)
Permissible rotation speeds:
N Design: 500 – 3000 rpm (max rotation speed 3500 rpm)
K Design: 500 – 3500 rpm
t (°C)
c
90
82
80
<
20 K
t
?
70
oh
60
R134a
50
40
30
20
-30
-20
-10
Fig. 4
3.4.2 Limits of application R407C (N and K versions)
Permissible rotation speeds:
N Design: 500 – 2600 rpm
K Design: 500 – 3500 rpm
t (°C)
c
61
60
t
<
20 K
?
oh
50
R407C
40
30
t + 25 °C
oh
20
-30
-20
-10
-25
Fig. 5
• FKX50/660 N
• FKX50/660 K
t + 25 °C
oh
0
10
20
0
10
Design for other ranges on request
• FKX50/775 N
• FKX50/775 K
operating pressure (g) high-
pressure side (HP): 28 bar
Unrestricted
application range
Reduced suction
gas temperature
Evaporation temperature (°C)
Condensing temperature (°C)
Suction gas superheat (K)
Suction gas temperature (°C)
t (°C)
30
o
operating pressure (g) high-
pressure side (HP): 28 bar
Unrestricted
application range
Reduced suction
gas temperature
Evaporation temperature (°C)
Condensing temperature (°C)
Suction gas superheat (K)
Suction gas temperature (°C)
t (°C)
20
o
Max. permissible
Max. permissible
D
GB
F
I
TR
CN
9