Setpoints Mode And Sub-Mode Directory - Carrier 38APS025 Manual

Gemini select, commercial air-cooled condensing units with comfortlink version 6.x controls 50/60 hz
Table of Contents

Advertisement

SUB-MODE
SPS.P
SPT.O
ST.P.O
COOL
P.CAP
L.C.ON
H.C.ON
L.C.OF
H.SP.F
HEAD
F.TME
NOTE: These values are values read or calculated by the controller
and cannot be changed from this item.
APPENDIX A — DISPLAY TABLES (cont)

Setpoints Mode and Sub-Mode Directory

ITEM
DISPLAY
CSP.1
XX.X °F (°C)
CSP.2
XX.X °F (°C)
XXX.X °F (°C)
XX.X F ( C)
XXX.X °F (°C)
XXX.X %
X.X F ( C)
XX.X F ( C)
X.X F ( C)
OAT.L
XX.X °F (°C)
H.SP
XXX.X °F (°C)
XX.X °F (°C)
F.ON
XXX.X °F (°C)
F.OFF
XXX.X °F (°C)
F.DLT
XX.X
F ( C)
XXX sec
ITEM DESCRIPTION
COOLING SET POINTS
Cooling Set Point 1
Cooling Set Point 2
Space T Cool Set Point
Space Temperature Offset
Space T SP Plus Offset
Percent Cap. Requested
Lo Cool On Set Point
Hi Cool On Set Point
Lo Cool Off Set Point
OAT Lockout Temperature
HEAD PRESSURE SET POINTS
Head Set Point On
Head Set Point Off
Fan On Set Point
Fan Off Set Point
Fan Stage Delta
Fan Delta Active Time
180
COMMENT
Range: 40 to 80 F (4.4 to 26.7 C)
Default: 60 F (15.6 C)
Range: 40 to 80 F (4.4 to 26.7 C)
Default: 55 F (12.8 C)
Range: 65 to 80 F (18.3 to 26.7 C)
Default: 78 F (25.6 C)
Recommended Setting: 78 F (25.6 C)
See Note
See Note
See Note
Range: –1.0 to 2.0 F (–0.6 to 1.1 C)
Default: 1.0 F (0.6 C)
Range: 0.5 to 20.0 F (0.3 to 11.1 C)
Default: 3.0 F (1.7 C)
Recommended Setting: 3.0 F (1.7 C)
Range: 0.5 to 2.0 F (0.3 to 1.1 C)
Default: 0.5 F (0.3 C)
Recommended Setting: 0.5 F (0.3 C)
Range: –20.0 to 80.0 F (-28.9 to 26.7 C)
Default: 30.0 F (–1.1 C)
Range: 85 to 120 F (29.4 to 48.9 C)
Default: 115 F (46.1 C)
Range: 45 to 90 F (7.2 to 32.2 C)
Default: 72.0 F (22.2 C)
See Note
See Note
Range: 0.0 to 50.0 F (0.0 to 27.8 C)
Default: 15.0 F (8.3 C)
Range: 0 to 300 seconds
Default: 60 seconds