F1, Sp2 And U7 Disable; F2, Heating Or Cooling Switch; F3, Alarm On/Off Switch; F4, Unit Display Enable - Process Technology DQ15D Installation, Operation And Calibration Manual

Digital temperature control
Hide thumbs Also See for DQ15D:
Table of Contents

Advertisement

Main Menu Summary

F1, SP2 and U7 Disable

This setting may be either a one (1) or a zero (0), and controls the
behavior of the DQ15D by making it perform like the single Set Point
PROCESS TECHNOLOGY model DE control. When this setting is set
to one (1), it is ON. The
Set Point and the U7 Power Save Set Point
SP2
are both disabled and will not work.

F2, Heating or Cooling Switch

This setting is not applicable for the DQ15D control.

F3, Alarm On/Off Switch

This setting may be a zero (0) or a one (1). When set to zero, the alarm Set
Point is turned off. When set to one, alarm Set Point is turned on.
The default value for this setting is zero (0).

F4, Unit Display Enable

This setting may be set to a zero (0) or a one (1). When set to one (1), the
DQ15D will display either a C or an F, separated by a decimal point. This
indicates that either Celsius or Fahrenheit is being displayed. If the
temperature being measured is greater than +999 degrees, the units are
not shown because the display is limited to four positions.
F5, Temperature Units Conversion
This setting may be set to a zero (0) or a one (1). When set to a zero (0),
the temperature is displayed in degrees Fahrenheit. When set to a one (1),
the temperature is displayed in degrees Celsius.
Conversion from F to C does NOT change Set Point or alarm upper limit
values. These must be changed manually.
The default setting is zero (0).
F6, Current Output Enable
This setting can be either zero (0), which is OFF, or one (1), which is ON.
When ON, it enables the optional current adder board on the DQ15D. See
for details on the current output signal.
4-20 mA Output Option
If the DQ15D is equipped with the optional 4-10 mA output feature, then
setting F6 to one (1) turns ON this feature. F6 must be ON before any
calibration can be performed.
The default setting is zero (0). Only active when using either of the optional 5416 or 5419
boards.
DQ15D Manual
M-34-01
22
Revision - Date: 01 - 04/23/08

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents