Power, Heating/Cooling; Extending Wiring - Process Technology DQ15D Installation, Operation And Calibration Manual

Digital temperature control
Hide thumbs Also See for DQ15D:
Table of Contents

Advertisement

Power, Heating/Cooling

Relay Equipment Needed
• #2 Phillips head screwdriver.
• 1/8 (x-small) straight blade
screwdriver.
• Power supply wire, 18 awg min
• Relay connection wires
Procedure
DQ15D is intended for a single
1
power source. Refer to the Power,
Heating and Cooling Relay Wiring
illustration when wiring DQ15D.
Locate and identify terminal
2
locations for the power supply
voltage, Set Point relay, and sensor.
Connect wires to the designated
3
terminals and tighten retaining
screw to secure the wire into place.
See state and local electrical require-
ments for proper 65°C wire gauge.
See the Specifications chart in the
beginning of this manual for Voltage,
Current, Frequency and other DQ15D
Specifications.
Over Temperature Protection Device with Low Level Cut-off Sample Wiring
M-34-01
Revision - Date: 01 - 04/23/08

Extending Wiring

Except when wiring thermocouples,
you can extend the factory supplied
1000 ohm RTD sensor with standard
22awg or larger electrical hookup
wire. The effect of an additional 22
awg sensor wire length on the value
is approximately 1°F for every 65 ft.
Warning
When dealing with THERMO-
COUPLES, you MUST use specific
thermocouple wire when extending
the sensor wire length. Use of
incorrect extension wire can cause
hazardous operating conditions.
Power, Heating /Cooling Relay Wiring
7
Wiring
DQ15D Manual