Configuration (Set-up)

RTD Error Messages

If the screen displays one of the
following messages, the control
relay de-energized due to an RTD
condition.
A thermocouple or RTD
HHH
sensor is improperly connected, or
the control read an open circuit.
The RTD sensor shorted.
UUU
Note: Thermocouple shorts cause a
new junction/measurement point to be
created. This will lead to false readings
and dangerous operating conditions.
Shorted thermocouples will not result
in an error condition. Instead, incorrect
readings will be displayed.
Configuration (Set-up)
To configure the DQ15D, press
1
and
simultaneously and hold
for approximately 6 seconds. The
screen displays
AC.0
While the 0 is flashing, use
2
change this to 11. Press
control will be in the configuration
mode. While in this mode, the
screen displays the values of
various configuration settings. The
first setting to display is the U1
setting. See setting summary. By
using
and
to scroll through the list of settings
to those needing modification.

Adjust Configuration Setting

To adjust a setting while in the
1
Configuration Mode, use
to bring the particular setting into
the view on the screen.
Press
to change the value of
2
SET
the setting. Once
released, the display will flash.
Use
and
3
the options for the selected setting.
M-34-01
Revision - Date: 01 - 04/23/08
.
. The
SET
keys, it is possible
and
has been
SET
to scroll through
After the option has been deter-
4
mined, press
the new value into memory.
After completing all changes to the
5
configuration of the control, the new
configuration must be saved. To save
the new value, press
neously. This will cause the control to
store the new values internally and
then reset the unit.

Sensor DIP Switch

When using the sensor 5416 or 5447
boards, an on-board DIP switch
must also be configured.
Sw
Sw
1
2
OFF OFF OFF
ON OFF OFF 100 ohm RTD
OFF ON OFF voltage
OFF OFF ON
OFF OFF OFF frequency
Note: Switching off power to the unit
before saving the new configuration will
to
cause all changes to be lost.
Dip Switch Location
(illustration shows DIP switch setting
18
once more to lock
SET
and
Sw
Type
3
1000 ohm RTD
current
for 100 ohm RTD)
simulta-
DQ15D Manual