U6, Sp2 Set Point Dead Band; U7, Power-Save Set Point Dead Band; U8, Display Stabilizer; L, Set Point Limit - Process Technology DQ15D Installation, Operation And Calibration Manual

Digital temperature control
Hide thumbs Also See for DQ15D:
Table of Contents

Advertisement

U6, SP2 Set Point Dead Band

This setting, which may be any number from +1 to +99, represents a dead
band that only applies to the
Temperature Sensor - Number represents degrees Celsius or Fahrenheit determined by
F5 setting
Voltage Sensor -Number represents tenths of a volt (0.1 VDC)
Current Sensor -Number represents hundredths of milliamps (0.01 mA)
Resistance Signal Devices -Number represents ohms
Frequency Signal Devices -Setting represents hertz (counts/second)
This bandwidth applies to the high side of the SP2 SET POINT. If the U6
setting is set at 5° F and the SP2 SET POINT is set at 115° F, then the Set
Point relay is de-energized when the (displayed) temperature reaches 115°
F and will remain de-energized until the temperature increases to 120° F.
Note: The default and minimum for the setting is one (1).

U7, Power-Save Set Point Dead Band

This setting, which may be any number from 1 to +99, represents a dead
band that only applies to the Power Save SET POINT.
Temperature Sensor - Number represents degrees Celsius or Fahrenheit as determined
by the F5 setting
Voltage Sensor -Number represents tenths of a volt (0.1 VDC)
Current Sensor -Number represents hundredths of milliamps (0.01 mA)
Resistance Signal Devices -Number represents ohms
Frequency Signal Devices -Setting represents hertz (counts/second)
If the Power Save SET POINT dead band setting is set at 10° F and the
Power Save SET POINT is 75°F, the SP1 relay de-energizes when the
temperature reaches 75° F and reenergizes when the temperature falls to 65°F.

U8, Display Stabilizer

If the display value changes by a digit or two in a steady state condition,
this setting can be altered in conjunction with the U4 setting to reduce the
display instability. Lower values cause maximum suppression. Larger
values provide greater accuracy. The default value for the U8, Display
Stabilizer setting is ten (10).

L, Set Point Limit

This setting, which may be any number between -99 and +999, is the
maximum limit for all
prevent accidental setting of a Set Point, which could be too high or low
(depending upon the application).
Temperature Sensor - Number represents degrees Celsius or Fahrenheit as determined
by the F5 setting
Voltage Sensor -Number represents tenths of a volt (0.1 VDC)
Current Sensor -Number represents hundredths of milliamps (0.01 mA)
Resistance Signal Devices -Number represents ohms
Frequency Signal Devices -Setting represents hertz (counts/second)
The default value for this setting is +999.
M-34-01
Revision - Date: 01 - 04/23/08
SP2 SET POINT
except the ALARM
SET POINTS
21
Main Menu Summary
. This is the cool Set Point.
SET POINT