Error Led On (Cpu Error) - Mitsubishi FX1N-14MR-ES/UL Hardware Manual

Fx1n series programmable controllers
Table of Contents

Advertisement

FX1N Series Programmable Controllers
7.2

ERROR LED ON (CPU ERROR)

Fault
POWER
RUN
ERROR
ERROR
LED ON
Remedy
Power OFF
Disconnect
earth/
A
ground
terminal
Power ON
Remedy
Possible program/scan time error.
Check D8012 for program scan time,
B
(units 0.2 ms must be less than 0.2 s,
i.e data value <2000).
Remedy
Reset PLC.
Power
Possible
OFF,ON
results
and trigger
RUN input.
LED is lit
Possible
results
LED is
flashing
Has the memory cassette been
LED OFF
installed or removed while the units
has still been powered?
LED is lit
A
B
Check for programming error. Ensure the earth/
ground cable is correctly rewired.
P C
M /C
P C
Possible results
D8012 > D8000
Diagnostics 7.
M /C
P C
M /C
7-2