Page 1
Installation Guide and Operating Manual FSX™ Fire and Flame Detectors Model FS17X™ FS17X WideBand IR™ Multi-Spectral Infrared Electro-Optical Digital W ideBand IR Sensor Radiant Energy Fire and Flame Detector...
Page 2
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
G2. Current sinking 4-20mA (+) & (-) ¹ Optional N.C. (Normally Closed) Relay Contacts are available. FS17X Configurations The Model FSX has several factory configurations to choose from: • Auxiliary: Alert (-R) or Fireball Quick Response (-S or -G) or Fire Verification (-G) •...
Speed of Response: Less than 5 seconds (typical) Quick Response: Less than 0.5 seconds to “fireball” type fires Spectral Sensitivity: 0.4 to 0.7 micron wavelengths NearBand IR 0.7 to 1.1 micron wavelengths WideBand IR 1.1 to 3.0 micron wavelengths Honeywell...
• FSC Windows® based PC Software for remote FSX diagnostics and data retrieval. • Designed, Manufactured, Tested, and Patented by Honeywell Analytics (30 years of proven fire / flame detection product excellence worldwide). Applications The applications for the FS17X Fire and Flame Detectors include:...
Page 7
Installation Guide and Operating Manual // Model FS17X™ Fire and Flame Detector Hydrogen Plants Hydrogen Storage Semiconductor Wet Benches Semiconductor Wet Chemicals Silane Gas Cabinets Silane Gas Manufacturing Honeywell...
There are no serviceable parts inside the Model FS17X Detector housing. If the Detector housing is opened up or tampered with, all warranties are voided Note: Do not attempt to modify the Model FS17X Detector as this voids all warranties. Honeywell...
The use of good wiring practices will simplify installation, improve reliability and facilitate maintenance. CAUTION: Follow static protection procedures while handling the connectors and the wiring of the FS17X Detector. Use a wrist strap connected to earth ground. Honeywell...
Page 10
The use of good wiring practices will simplify installation, improve reliability and facilitate maintenance. CAUTION: Follow static protection procedures while handling the connectors and the wiring of the FS17X Detector. Use a wrist strap connected to earth ground. Honeywell...
Page 11
The use of good wiring practices will simplify installation, improve reliability and facilitate maintenance. CAUTION: Follow static protection procedures while handling the connectors and the wiring of the FS17X Detector. Use a wrist strap connected to earth ground. Honeywell...
After the Detector(s) is powered, as with all flame and fire Detectors, conduct an external Detector test “end to end”. Using an external FSC FSX hand-held test lamp ensures that the FS17X Detector has a clear unobstructed view of the threat area and the Detector is aimed properly at the fire threat area.
Page 13
To test the full functionality of a FSX Detector, use either the Model TL1055X or TL2055X Test Lamp in the manner prescribed in this Instruction Manual.
Page 14
Remember to disable the Detector outputs, as a full functional test includes activating the alarm outputs. A FSX Honeywell Analytics Test Lamp must be used for this test (Section 4.3). Point the Test Lamp directly at the front of the Detector (on axis as much as possible, within a distance of 1 to 25 feet). Activate the Test Lamp by pressing and holding its pushbutton.
IR detectors. FSC’s patented FSX Fire Detectors also use two additional spectral regions, the Visible Band, that spans from about 400 to 700 nanometers (0.4 to 0.7 microns) and the NearBand IR that span from about 0.7 to 1.1 microns.
LED Status Indicators As with all FSX Detectors, the Model FS17X Detector uses three (3) separate, bright LED’s (rather than one tri-colored LED that can be difficult to recognize the different colors outdoors or in a brightly lit area) to indicate the Detector’s status.
In addition to the Remedies listed above, cycle (re-apply) primary input power to the Detector. If any of the Faults listed above continues after taking the appropriate remedy, contact a Technical Representative at Honeywell Analytics. It may be necessary to obtain a Return Merchandise Authorization Number (RMA #) and return the Detector to the Factory.
Additionally, semi-annual or quarterly testing should be performed, using the correct Honeywell Analytics Test Lamp, to ensure the integrity of the entire fire protection system. (see Note in Section 2.4 and Section 4.3) Clean the FS17X Detector window: •...
Honeywell Analytics warrants its Products against defects in material and workmanship under normal use and service for a period of two (2) years from the date of shipment as described herein. Honeywell Analytics, at its option, will repair or replace, at no charge, such products found to be defective during the warranty period provided that they are returned in accordance with the terms of this warranty.
Installation Guide and Operating Manual // Model FS17X™ Fire and Flame Detector Laws in the United States and other countries preserve for Honeywell Analytics certain exclusive rights for copyrighted Honeywell Analytics software/firmware, such as the exclusive rights to reproduce in copies and distribute copies of such Honeywell Analytics software/firmware.
Page 21
Non-Latching (Standard) Relay Contacts Alert & Alarm Normally Open and Normally De-Energized, Fault Normally Closed and Normally Energized (Standard) Outputs Fault, Alert & Alarm Relays with FireBusII (Standard) Detector Sensitivity High Sensitivity (Standard) Detector Type - Application Radiant Energy (Standard) Honeywell...
ALARM outputs are functioning properly. (see Note in Section 2.4) For calibrated testing, in compliance with NFPA 72 Codes for flame detectors, as manufacturers of the FSX product line, our calibrated testing using our TL-2055X Test Lamp is as follows. If the FS17X set at Highest Sensitivity ALARMS to a fully charged TL-2055X Test Lamp at a distance between 1 and 25 feet, then the FS17X is in normal operating condition.
Installation Guide and Operating Manual // Model FS17X™ Fire and Flame Detector Drawings 4.4.1 Outline and Dimensions Figure 4-3 Outline & Dimesional Drawing for Model FS17X Honeywell...
ALARM relay contacts shown with no power applied. ALARM relay is normally De-Energized during normal operation and with no ALARM. This relay will Energize during ALARM conditions. Fault relay contacts shown with no electrical power applied. During normal operation and with no Fault, this relay will De- Energize and the N.O. (Normally Open) contacts will close. Honeywell...
Page 25
Fault relay contacts shown with no electrical power applied. During normal operation and with no Fault, this relay will De-Energize and the N.O. (Normally Open) contacts will close. EOL (End-Of-Line) device shall be installed as required and supplied by the Fire Alarm Panel. Honeywell...
Page 26
ALARM. This relay will Energize during ALARM conditions. 3. Fault relay contacts shown with no electrical power applied. During normal operation and with no Fault, this relay will De-Energize and the N.O. (Normally Open) contacts will close. Honeywell...
Page 27
Fault relay contacts shown with no electrical power applied. During normal operation and with no Fault, this relay will De- Energize and the N.O. (Normally Open) contacts will close. EOL (End-Of-Line) device shall be installed as required and supplied by the Fire Alarm Panel. Honeywell...
Orange Fire Alert Relay Terminal B Yellow with Fire Alert Relay Terminal A Loop-Through Black Stripe Orange with Fire Alert Relay Terminal B Loop-Through Black Stripe Figure 4-13 FS17X-RHA1N- 4.4.3 Detector Label Drawings Figure 4-14 Model FS17X Detector Label Honeywell...
Honeywell Analytics Asia Pacific Co., Ltd. #701 Kolon Science Valley (1) 43 Digital-Ro 34-Gil, Guro-Gu Seoul, 152-729 Korea Email: analytics.ap@honeywell.com Internet These Honeywell websites may be of interest to Industry Solution customers. Honeywell Organization Corporate www.honeywell.com Honeywell Analytics www.honeywellanalytics.com Telephone Contact us by telephone at these numbers.