Chappee initia MASTER 2.24 FF Installers And Users Instructions page 10

High efficiency wall-mounted gas-fired boilers
Table of Contents

Advertisement

Available languages

Available languages

Separated horizontal flue terminals installation options
Fr
IMPOrTANT: Ensure a minimum downward slope of 1 cm toward the outside per each
metre of duct length.
CN
GB
Gr
SP
PT
NB: For C52 types, terminals for combustion air suction and combustion product extrac-
tion must never be fitted on opposite walls of the building.
Separated vertical flue terminals installation options
Important: if fitting a single exhaust flue duct, ensure it is adequately insulated (e.g.: with
glass wool) wherever the duct passes through building walls.
For detailed instructions concerning the installation of fittings refer to the technical data
accompanying the fittings.
Split flue air control adjustment
The adjustment of this control is required to optimise performance and combustion param-
eters. The air suction coupling can be rotated to adjust excess air according to the total
length of the flue and intake ducts for the combustion air.
Turn this control clockwise to increase excess combustion air and anticlockwise to
decrease it.
(L1 + L2) max = 30 m
L max = 12 m
In the event of installation of the condensate collection kit, the angle of the drain duct
must be directed towards the boiler.
The maximum length of the suction duct must be 10 metres.
If the flue duct exceeds 6 m, the condensate collection kit (supplied as an accessory)
must be fitted close to the boiler.
L max = 10 m
L max = 10 m
To improve optimisation a combustion product analyser can be used to measure the CO
contents of the flue at maximum heat output, gradually adjusting air to obtain the CO
reading in the table below, if the analysis shows a lower value.
To properly install this device, also refer to the technical data accompanying the fitting.
48