12.8 Timer Control

There are 2 sets of ON and OFF timer is available to turn the unit ON or OFF at different preset time.
If more than one timer had been set, the upcoming timer will be display and will activated in sequence.
12.8.1
ON Timer Control
ON Timer 1 and ON Timer 2 can be set using remote control, where the unit with timer set will start operation earlier
than the setting time. This is to provide a comfortable environment when reaching the set ON time.
60 minutes before the set ON time, indoor (at fan speed of Lo-) and outdoor fan motor start operation for 30 seconds
to determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting
time.
From the above judgment, the decided operation will start operation earlier than the set time as shown below.
12.8.2
OFF Timer Control
OFF Timer 1 and OFF Timer 2 can be set using remote control, where the unit with timer set will stop at set OFF time.
Notes:
1
By pressing ON/OFF operation button, the ON Timer or OFF Timer setting will not be cancelled.
2
To cancel the previous timer setting, press CANCEL button.
3
To activate the previous timer setting, press SET button.
4
If main power supply is switched off, the Timer setting will be cancelled.
12.9

Random Auto Restart Control

When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes. There are 10 patterns to be selected randomly after power supply resumes.
This control is not applicable during OFF/ON Timer setting.
This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.

12.10 Indication Panel

LED
POWER
Color
Green
Light ON
Operation ON
Light OFF
Operation OFF Timer Setting OFF Quiet Mode OFF Powerful Mode OFF
Note:
If POWER LED blinks, the possible operation of the unit is operation mode judgment, or ON timer sampling.
If TIMER LED blinks, there is an abnormal operation occurs.
If e-ion LED blinks, there is an abnormal e-ion operation occurs.
If PATROL LED blinks, there is gas sensor error detection.
Indoor intake air
temperature (°C)
30
25
5 min
Cooling / Soft Dry
TIMER
QUIET
Orange
Orange
Timer Setting ON
Quiet Mode ON
15 min
10 min
Outdoor air
30
35
temperature (°C)
POWERFUL
Orange
Powerful Mode ON
66
e-ion
PATROL
Blue
Blue
Orange
e-ion ON
Air Clean
Moderate
e-ion OFF
PATROL OFF
Red
Dirty