Compressor Overheating Prevention Control (For S18, S24Mk, S28Mk Only); Low Pressure Prevention Control (Gas Leakage Detection); Compressor Tank Temperature Rise Protection Control; Low Frequency Protection Control 1 - Panasonic CS-S9MKQ Service Manual

Hide thumbs Also See for CS-S9MKQ:
Table of Contents

Advertisement

13.4.2
S18MK, S24MK, S28MK
Overheating Prevention Control
When the IPM temperature rises to 100°C, compressor operation will stop immediately.
o
Compressor operation restarts after 3 minutes the temperature decreases to 95°C.
o
DC Peak Current Control
When electric current to IPM exceeds set value of 18.5A, the compressor will stop operate.
o
During operation starts, if the DC peak current is detected after 30 seconds, the operation will restart
after 2 minutes.
During operation starts, if the DC peak current is detected within 30 seconds, the operation will restart
after 1 minute.
After compressor starts for 30 seconds, if DC peak current is detected exceeding 18.5A and this condition
o
repeats continuously for 7 times, all indoor and outdoor relays will be cut off. Timer LED blinks and "F99"
indicated.
13.5 Compressor Overheating Prevention Control (For S18, S24MK, S28MK
only)
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
If compressor discharge temperature exceeds 112°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. "F97" is indicated.

13.6 Low Pressure Prevention Control (Gas Leakage Detection)

Control start conditions
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o
During Cooling and Soft Dry operation:
o
Indoor suction temperature – indoor piping temperature is below 4°C
Control contents
Compressor stops (and restart after 3 minutes).
o
If the conditions above happened 2 times within 20 minutes, the unit will:
o
Stop operation
Timer LED blinks and "F91" indicated.

13.7 Compressor Tank Temperature Rise Protection Control

Control start conditions
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o
During Cooling and Soft Dry operation:
o
Indoor suction temperature -indoor piping temperature is below 4°C.
Indoor temperature and outdoor temperature is 30±5°C.
Remote Control setting 16°C and Hi Fan Speed.
Control contents
Compressor stops (and restart after 3 minutes)
o
If the conditions above happened 2 times within 20 minutes, the unit will:
o
Stop operation
Timer LED blinks and "F91" indicated.

13.8 Low Frequency Protection Control 1

When the compressor operates at frequency lower than 24Hz continued for 20 minutes, the operation frequency
will be changed to 23Hz for 2 minutes.
Compressor=OFF
112°C
Compressor Frequency
Reduced
110°C
Compressor Frequency
100°C
Maintain
Comp Discharge temperature
80
97°C
96°C
90°C
Free