VACON · 154
Fault
Fault
code
38 **
Device added
(same type)
39 **
Device removed
40
Device unknown
41
IGBT temperature
42
Brake resistor
overtemperature
43
Encoder fault
10
Subcode in
Possible cause
T.14
The option board was added.
You have used the same
option board before in the
same slot. The parameters
are available in the drive.
An option board was
removed from the slot.
S1 =
An unknown device was
Unknown
connected (the power unit/
device
option board)
S2 =
Power1not
same type
as Power2
IGBT Inverter Bridge over-
temperature protection has
detected too high a short
term overload current.
Brake resistor overtemper-
ature protection has detec-
ted too heavy braking.
1 =
Problem detected in
Encoder 1
encoder signals.
channel A
is missing
2 =
Encoder 1
channel B
is missing
3 = Both
encoder 1
channels
are miss-
ing
4 =
Encoder
reversed
5 =
Encoder
board
missing
FAULT TRACING
How to correct the fault
Reset the fault. The device is ready
for use. The drive starts to use the
old parameter settings.
The device is not available. Reset
the fault.
Ask instructions from the distribu-
tor near to you.
Do a check of the loading.
Do a check of the motor size.
Make an identification run.
Set the deceleration time longer.
Use external brake resistor.
Do a check of the encoder connec-
tions.
Do a check of the encoder board.
Do a check of the encoder fre-
quency in the open loop.