Danfoss VLT 2800 Quick Manual page 32

Frequency converter
Hide thumbs Also See for VLT 2800:
Table of Contents

Advertisement

VLT 2800 Quick Guide
Accuracy on frequency output
Resolution on frequency output
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals. See section entitled Galvanic Isolation in the Operating Instructions.
Control card, analog output:
Number of programmable analog outputs
Terminal number
Current range at analog output
Max. load to common at analog output
Accuracy on analog output
Resolution on analog output
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals. See section entitled Galvanic Isolation in the Operating Instructions.
Control card, 24 V DC output:
Terminal number
Max. load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV) , but has the same
potential as the analogue and digital inputs and outputs. See section entitled Galvanic Isolation
in the Operating Instructions.
Control card, 10 V DC output:
Terminal number
Output voltage
Max. load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals. See section entitled Galvanic Isolation in the Operating Instructions.
Control card, RS 485 serial communication:
Terminal number
Terminal number 67
Terminal number 70
Full galvanic isolation. See section entitled Galvanic Isolation in the Operating Instructions.
For CANopen/DeviceNet units, see VLT 2800 DeviceNet manual, MG.90.BX.YY.
Relay outputs:
Number of programmable relay outputs
Terminal number, control card (resisitvie and inductive load)
Max. terminal load (AC1) on 1-3, 1-2, control card
Max. terminal load (DC1 (IEC 947)) on 1-3, 1-2, control card
Min. terminal load (AC/DC) on 1-3, 1-2, control card
The relay contact is separated from the rest of the circuit by strengthened isolation.
Note: Rated values resistive load - cosΦ >0.8 for up to 300,000 operations.
Inductive loads at cosΦ 0.25 approximately 50% load or 50% life time.
Cable lengths and cross sections:
Max. motor cable length, screened/armoured cable
Max. motor cable length, unscreened/unarmoured cable
Max. motor cable length, screened/armoured cable and motor coil
Max. motor cable length, unscreened/unarmoured cable and motor coil
Max. motor cable length, screened/armoured cable and RFI/1B filter
Max. motor cable length, screened/armoured cable and RFI/1B filter
Max. motor cable length, screened/armoured cable and RFI 1B/LC filter
Max. cross section to motor, see next section.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
1)
Max. error: 0.2 % of full scale
0/4 - 20 mA
Max. error: 1.5 % of full scale
10.5 V ±0.5 V
68 (TX+, RX+), 69 (TX-, RX-)
Common for terminals 67, 68 and 69
1-3 (break), 1-2 (make)
250 V AC, 2 A, 500 VA
25 V DC, 2 A /50 V DC, 1A, 50W
24 V DC 10 mA, 24 V AC 100 mA
200 V, 100 m
400 V, 25 m
400 V, 25 m
1 Quick Guide
1
10 bit
1
42
500 Ω
10 bit
12
130 mA
50
15 mA
+ 5 V
1
40 m
75 m
100 m
200 m