ICM Controls i3 2010WR Installation, Operation & Application Manual page 16

Table of Contents

Advertisement

9. Outdoor Upper Setpoint (50°F to 25°F, – –) (10°C to -4.0°C, – –)
WARNING!: Incorrect settings can damage system and/or cause potentially dangerous
conditions. Use the code described in Configuration Safety Lock.
Note: Select upper setpoint for chart on previous page. Select
Press the
or
to select.
Press
to advance to the next screen.
10. Outdoor Lower Setpoint (select – – to disable)
Appears only for heat pump with electric backup with outdoor upper setpoint enabled.
Note: Select lower setpoint for chart on previous page.
Press the
or
to select temperature.
Press
to advance to the next screen.
11. Auxiliary Delay ON (0-60 minutes)
Set the delay time in minutes for auxiliary heat to be locked out after a call for second stage. This
extra savings feature is used to temporarily lock out auxiliary heat devices, allowing just heat pump to
try to satisfy heat call.
Press the
or
to select.
Press
to advance to the next screen.
12. Lockout (0-8°, SLEEP, COOL-HEAT)
Select the number of degrees set temperature can be changed during keypad lockout. SLEEP
setting locks thermostat only during the sleep period to prevent after hours tampering. COOL-HEAT
lockout allows adjustment of the set temperatures to the maximum heat set temperature selected and
minimum cool set temperature selected.
Note: The mode cannot be changed while the thermostat is locked.
Press the
or
to select.
Press
to advance to the next screen.
13. Maximum Heat Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the maximum heat set temperature allowed.
Press the
or
to select.
Press
to advance to the next screen.
16
to disable.
Hi
CONFIG
CONFIG
Low
HEAT
CONFIG
CONFIG
HEAT
CONFIG