8.5.2

Reset

RESET
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset
response (Page 363)").
The following settings can be selected:
● Automatic reset (Memory = O / Mem = no)
The device is reset automatically as soon as a previously occurring error has been dealt
with.
● Manual RESET (Memory = I / Mem = yes)
To reset the devices with digital setting, it is necessary to press both arrow keys
simultaneously for more than 2.5 s after removal of the cause of error. If the cause of the
error has not been removed, a new error message appears immediately. Alternatively,
the devices can be reset by switching the rated control supply voltage on and off.
Note
The warning threshold is always reset by autoreset.
3UG4 / 3RR2 monitoring relays
Manual, 05/2016, NEB927043002000/RS-AC/004
3UG4625 residual current monitoring relay with 3UL23 transformer