3UG4625 residual current monitoring relay with 3UL23 transformer

8.4 Operation

8.4
Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
Parameter information
The following table lists the adjustable parameter information for the 3UG4625 residual
current monitoring relay:
Table 8- 2
Parameter information, 3UG4625 residual current monitoring relays with digital setting
Menu
Parameters
level
"RUN" Threshold for overshoot (I▲) 0.03 A
"RUN" Warning threshold for
overshoot (I!)
"SET"
Hysteresis (Hyst)
"SET"
Initialization (Init)
"SET"
ON-delay time (onDel)
"SET"
Tripping delay time (I▲Del)
"SET"
Reset response (Mem)
"SET"
Relay switching behavior
(closed-circuit principle NC /
open-circuit principle NO)
Note
Various parameters are deactivated by setting OFF.
The parameters are described in the Chapter "Parameters (Page 363)".
Menu-based operation is described in the Chapter "Menu-based operation (Page 39)".
The 3UL23 residual current transformers used cover the entire fault current range from
0.03 to 40 A in all sizes.
For more information on the technical data of 3UL23 residual current transformers see
Chapter "Technical data (Page 346)".
202
Setting range
Minimum value
Maximum value
40.0 A
0.03 A or OFF
40.0 A
OFF (0 %)
50 %
ERR
OK
0.1 s or OFF
20.0 s
0.1 s or OFF
20.0 s
no = Autoreset
yes = Hand-RESET
NC or NO
Increment
Depending on the value,
0.01 A or 0.1 A
Depending on the value,
0.01 A or 0.1 A
5 %
--
0.1 s
0.1 s
--
--
3UG4 / 3RR2 monitoring relays
Manual, 05/2016, NEB927043002000/RS-AC/004
Factory setting
1.0 A
0.5 A
5 %
ERR
OFF
0.1 s
no = Autoreset
NC