Operation - Siemens 3UG4 User Manual

Industrial controls monitoring and control devices
Hide thumbs Also See for 3UG4:
Table of Contents

Advertisement

3UG463. voltage monitoring relay

10.4 Operation

10.4
Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
Parameter information
The table below shows the settable parameter information of the 3UG463. voltage
monitoring relays:
Table 10- 2
Parmeter information, 3UG463. voltage monitoring relays with digital setting
Menu
Parameters
level
"RUN"
Threshold for undershoot (U▼)
"RUN"
Threshold for overshoot (U▲)
"SET"
Hysteresis (Hyst)
"SET"
ON-delay time (onDel)
"SET"
Tripping delay time (
"SET"
Reset response (Mem)
"SET"
Relay switching behavior
(closed-circuit principle NC /
open-circuit principle NO)
3UG4631 voltage monitoring relay
1)
3UG4632 voltage monitoring relay
2)
3UG4633 voltage monitoring relay
3)
Note
The monitoring mode "Overshoot" or "Undershoot" is defined with the setting OFF at the
threshold for undershoot or overshoot.
Note
Deactivating monitoring
If the upper and lower threshold values are deactivated (OFF), monitoring will cease for:
• Voltage overshoot
• Voltage undershoot
The up-to-date measured value is displayed permanently.
The parameters are described in Chapter "Parameters (Page 363)."
Menu-based operation is described in Chapter "Menu-based operation (Page 39)."
278
Setting range
Minimum value
0.1 V or OFF
1)
10 V or OFF
2)
17 V or OFF
3)
0.1 V or OFF
1)
10 V or OFF
2)
17 V or OFF
3)
0.1 V
0.1 s
3)
0.1 s
)
no = Autoreset
NC
Increment
Maximum value
60 V
0.1 V
1)
600 V
2)
275 V
3)
60 V
0.1 V
1)
600 V
2)
275 V
3)
30 V
0.1 V
1)
300 V
2)
150 V
3)
20 s
0.1 s
3)
20 s
0.1 s
yes = Hand-RESET
--
NO
--
Manual, 05/2016, NEB927043002000/RS-AC/004
Factory setting
20 V
1)
170 V
2), 3)
30 V
1)
260 V
2),3)
2 V
1)
5 V
2), 3)
0.1 s
3)
3)
0.1 s
no = Autoreset
NC
3UG4 / 3RR2 monitoring relays

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3rr2

Table of Contents