3UG463. voltage monitoring relay
10.7 Technical data
Impulse voltage
resistance rated
value
Recorded real
power
Protection class IP
Electromagnetic
compatibility
Operating current at
17 V minimum
Continuous current
of the DIAZED fuse
link of the output
relay
Resistance against
vibration according
to IEC 60068-2-6
Resistance against
shock according to
IEC 60068-2-27
Installation altitude
at a height over
sea level maximum
Maximum permissible
voltage for safe
disconnection
between control
and auxiliary
circuit
between auxiliary
circuit and
auxiliary circuit
Conductor-bound
parasitic coupling
BURST according to
IEC 61000-4-4
Conductor-bound
parasitic coupling
conductor-earth
SURGE according
to IEC 61000-4-5
Conductor-bound
parasitic coupling
conductor-conductor
SURGE according
to IEC 61000-4-5
Electrostatic
discharge according
to IEC 61000-4-2
286
3UG463.-1.A
3UG463.-1.L 3UG463.-1.W 3UG463.-2.A 3UG463.-2.L 3UG463.-2.W
kV
4
W
2
IP20
IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4
mA
5
A
4
1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g
sinusoidal half-wave 15g / 11 ms
m
2 000
V
300
V
300
2 kV
2 kV
1 kV
6 kV contact discharge / 8 kV air discharge