2 PROFIBUS DP COMMUNICATION ACCESSORY

The following Profibus DP accessory is needed in order to enable the device communication in a Profibus DP
network. Information about the installation of this module can be found in the guide that came with the
accessory.
2.1

PLUG-IN MODULE CFW500-CPRO

2.2

CONNECTOR PINOUT

The Profibus DP-V1 communication module has two connectors to the Profibus network, each one with the
following pinout:
NOTE!
The DB9 connector frame is connected to the frequency inverter protective earth.
2.3

INDICATIONS

The alarms, faults and status indications are done through the device HMI and parameters.
2.4

DIP SWITCHES

At each segment of the Profibus DP network, it is necessary to enable terminating resistors at both end points
of the main bus. For this purpose, the Profibus DP communication module has two DIP switches that can be
activated (both switches to the ON position) to enable the resistor. The DIP switches should not be activated if
the network connector already has the terminating resistors.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
WEG part number: 11769750.
Composed by the Profibus DP-V1 communication module and an
installation guide.
It supports DP-V1 (acyclic messages).
Table 2.1: Profibus female DB9 connector pinout (XC6)
Pin
Name
1
-
-
2
-
-
3
B-Line (+)
RxD/TxD positive (red)
4
RTS
Request To Send
5
GND
0V isolated for the RS485 circuit
6
+5V
+5V isolated for the RS485 circuit
7
-
-
8
A-Line (-)
RxD/TxD negative (green)
9
-
-
Function