4-4-21 Compressor Discharge or Top temperature sensor breakaway error
Outdoor unit display
Indoorunit display
※ ● : ON ◑ : Flash ×: OFF
1) Faulty compressor frequency of 60Hz or higher.
2) Suction temperature > Low pressure saturation temperature +10 ℃
Judgment Method
3) Relevant discharge or Top temperature < High pressure saturation temperature
4) In case of keep 30 minutes in state that satisfy all above conditions (1,2&3) for 30min.
Cause of problem
∙ Compressor discharge or Top temperature sensor breakaway and defective / Ineffective start of compressor
1. Cause of problem
Is the Discharge
or Top temperature sensor and the sensor holder
correctly attached?
Is the Discharge or Top temperature
sensor resistance value reasonable?
(Refer to the "Note 1")
Replace the PCB
Samsung Electronics
(Compressor 1 Discharge)
(Compressor 1 Top)
Duct, Cassette (1/2 Way),Console, Celing
Operation Defrost
Timer
Fan
×
×
◑
◑
Yes
Yes
(Compressor 2 Discharge)
(Compressor 2 Top)
Cassette (4/Mini4 Way)
Filter/MPI Operation Defrost
Timer
◑
◑
◑
×
No
No
Resistance value
Resistance value
measure part
measure part
TOP1
TOP2
TOP1 : CN43 (3, 4)
TOP2 : CN45 (5, 6)
DIS1 : CN43 (1, 2)
DIS2 : CN45 (3, 4)
Wall-mounted (NeoForte)
Filter
Operation Timer
Turbo
◑
×
×
◑
Re-insert sensor Re-attach sensor holder
Defective sensor : Replace sensor
NOTE1
Temperature(°C)
130
120
100
80
60
25
20
10
0
Troubleshooting
24℃
27℃
◑
◑
Resistance(KΩ)
8.9
11.2
18.5
32.0
59.0
200.0
242.0
362.0
553.0