How to set the key function of the outdoor unit
AM
XV
Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Emergency operation for
Individual
compressor malfunction
Capacity correction for
cooling
Capcity correction for
heating
Current restriction rate
Individual
Oil collection interval
Temperature to trigger
defrost operation
Fan speed correction for
Individual
outdoor unit
Silent mode for
night-time
High-head
condition setting
Samsung Electronics
0
0
0
0
0
0
0
0
Main
0
1
0
0
0
0
0
0
0
0
Main
0
2
0
0
0
0
0
0
0
0
0
0
0
0
3
0
0
0
0
0
0
0
Main
0
4
0
0
Main
0
5
0
0
0
6
0
0
0
0
Main
0
7
0
0
0
0
0
0
Main
0
8
0
0
(cont.)
Function of the option
0
Disabled (Factory default)
Set compressor 1 as malfunction
1
state
Set compressor 2 as malfunction
2
state
7-9 (Factory default in case
0
of A type PBA)
5-7 (Factory default in case of
1
B type PBA)
2
9-11
3
10-12
4
11-13
5
12-14
6
13-15
0
3.0 (Factory default)
1
2.5
2
2.6
3
2.7
4
2.8
5
2.9
6
3.1
7
3.2
8
3.3
0
100% (Factory default)
1
95 %
2
90 %
3
85 %
4
80 %
5
75 %
6
70 %
7
65 %
8
60 %
9
55 %
0
50 %
1
No restriction
0
Factory default
1
Shorten the interval by 1/2
0
Factory default
Apply setting when the product is
1
being installed in humid area
such as near river or lake
0
Factory default
1
Increase fan speed
0
Disabled (Factory default)
1
LEVEL 1 / Auto
2
LEVEL 2 / Auto
3
LEVEL 3 / Auto
4
LEVEL 1 / External contact
5
LEVEL 2 / External contact
6
LEVEL 3 / External contact
0
Disabled (Factory default)
Level 1 of height difference type 1
1
(indoor unit is lower than
outdoor unit)
Level 2 of height difference type 1
2
(indoor unit is lower than
outdoor unit)
Height difference type 2
3
(Outdoor unit is lower than
outdoor unit)
Key Options
Remarks
E560 will occur when all the
compressors are set as malfunction
state.
Targeted evaporation
temperature[°C]
(When low temperature value is set,
discharged air temperature of the
indoor unit will decrease)
Targeted high pressure [MPa]
(When low pressure value is set,
discharged air temperature
of the indoor unit will decrease)
When restriction option is set,
cooling and heating performance
may decrea
Increase the outdoor unit's fan
speed to maximum value
Enable silent mode for night-time
(It operates automatically
depending on the temperature.)
However, if the external contact
interface module (MIM-B14)
is used, entering the silent mode is
available with contact signal.
When outdoor unit is located
40~80m above the indoor unit
When outdoor unit is located over
80m above the indoor unit
When indoor unit is over 30m
above the outdoor unit