Communication Error Between Indoor And Outdoor Units After Tracking - Samsung AM072FXVAFH series Service Manual

Am0724fxvafh
Table of Contents

Advertisement

Troubleshooting

4-4-4 Communication Error between Indoor and Outdoor Units after Tracking

Outdoor unit display
Indoorunit display
Judgment Method
∙ Outdoor unit is unable to communicate for two minutes during operation. (no reception of relocation)
Cause of problem
∙ Communication error between indoor and outdoor units and setup error of indoor unit installation quantity setup switch.
1. How to check
Press the reset key (K3) of the outdoor unit PCB
and check the display module.
response at all from the display module during
Remove the communication cable that connects
the outdoor unit to the indoor nit, and measure
the 2 outdoor unit cables with a scope.
the 2 cables a square wave with DC±0.7V or more
as shown in the image below?
Connect the communication cable again to
connect the outdoor unit to the indoor unit.
Remove all the communication connectors on the PCB of
the indoor unit, and connect them one by one to find
the indoor unit which interferes with the communication
to check and change the indoor unit PCB.
0.7V
0.7V
4-30
Duct, Cassette (1/2 Way),Console, Celing
Operation Defrost
Timer
Fan
×
×
※ ● : ON ◑ : Flash × : OFF
Is there no indoor unit
the tracking?
Yes
Is the voltage between
Yes
Cassette (4/Mini4 Way)
Filter/MPI Operation Defrost
Timer
×
×
No
After two minutes, find the indoor unit which displays
the communication error and check if the PCB address
(Communication error occurs if the indoor unit
addresses are overlapped.)
- In this case, the communication error will occur in every
indoor unit (2 or more units) with the address incorrectly
If there is no peculiarity in the address, check
the communication cable and change the indoor unit PCB.
No
Check the communication cable and the
* Essential Requirements before Changing PCB in
Case of Communication Error: Refer to p.50
Good
Wall-mounted (NeoForte)
Filter
Operation Timer
Turbo
×
×
×
settings are overlapped.
set.
connector for the outdoor unit PCB,
and change the PCB.
Defective
Samsung Electronics
24℃
27℃
×

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents