Indications On The Inverter Display (Cfw100) - WEG CFW100 Installation And Operation Manual

Flash memory module
Hide thumbs Also See for CFW100:
Table of Contents

Advertisement

Available languages

Available languages

Flash Memory Module
State
PARAM
PASTE
ERROR
SOFTPLC
PASTE
ERROR
The possible causes of the "ErrC" and "ErrP" errors are:
Low battery during the transfer.
Disconnection of the cable during the transfer.
Incompatibility of firmware versions during download
of the inverter parameter table (paste function)
indicating "ErrP" on the display.
6 INDICATIONS ON THE INVERTER
DISPLAY (CFW100)
State
NORMAL
FAULT
ALARM
The possible causes of F082 fault are:
Data transfer using the paste function
(CFW100-MMF → CFW100) with invalid data and/or
incompatible software version.
Attempt of connection and data transfer with the
(CFW100) inverter energized.
The possible causes of alarm A712 are:
Attempt to copy SoftPLC program protected against
copies ("never permit to copy").
Attempt to copy the SoftPLC program from a
protected copy ("never permit to copy from a copy").
8 | CFW100
HMI
Indicates an error occurred in the
download
(CFW100-MMF → CFW100) of
the inverter parameter table.
Indicates an error occurred in the
download
(CFW100-MMF → CFW100) of
the inverter SoftPLC application.
HMI
Normal operating condition.
Indication of communication fault
between the CFW100-MMF and
the CFW100 (F082). This fault
can be reset by means of the
switch indicated in
page
Alarm indication in the attempt
to copy protected SoftPLC user
program from the CFW100.
Description
Description
Figure A.3 on
21.