● nvoFanStatus(15), nviFanStatus(4)
Description
SNVT Type
Value and operation
● nvoERVMode(16), nviERVMode(5)
Description
SNVT Type
Value and operation
● nvoErrorCode(17)
Description
SNVT Type
Value and operation
Fan Speed and direction
SNVT_switch: Unsigned/signed Short
Value
Auto
0.0
Low
1.0
Mid
2.0
High
3.0
Eco
4.0
Turbo
5.0
Any>5.0
Auto
Stop
-
Up-Down
-
❈ Supporting modes are different according to indoor units.
- Indoor unit: Auto, Low, Mid, High (Turbo : Optional)
- ERV : Mid, High, Turbo
- AHU Kit: High
* When an indoor unit operation mode is Auto or Dehumid,
Fan speed is controlled as 'Auto' .
* When an indoor unit operation mode is FAN ONLY, 'Auto'
cannot be controlled by Fan speed.
ERV Operation Mode
SNVT_count: Unsigned Long, 2 bytes
( 0: Auto )
1: H/R
( 2: Air purification )
3: Sleep
4: Normal
❈ ( ) : Function that is not supported now.
Error Code
SNVT_count: Unsigned Long, 2 bytes
Valid Range: 0 ~ 999
00 00 → No Error
Refer to list of Error code
State
-
-
-
-
-
-
0
1
87
E-