Installing the DMS2.5 (Continued)
Using the DI External Contact Control (Optional)
Setting the External Contact Control Pattern
You can set the system settings through contact control pattern.
1
Select [System Settings] menu and click [System environment setting].
2
Click [Edit] from 'Select the contact control pattern' .
3
Select the pattern you want to check.
Pattern 1[No external input]: No operation will be made when inputting
contact point control signal.
Pattern 2[Level(Emergency stop)]: Commands that stop all indoor unit
operation and disable remote control when inputting contact point control
signal. In level emergency stop status, it will not be controlled even if the
command is set from upper controller.
Pattern 3[Level(Operation/Stop)]: Level signal input timing.
It changes operation/stop status of all indoor units.
Pattern 4[pulse (Operation/Stop,Disable/Enable)]:
Pulse signal. It changes operation/stop status of all indoor units.
4
Click [Save] after setting is completed.
5
Click [OK] when "This information will be modified. Do you want to proceed?"
message window appears.
6
"Reading data from DMS2.5. Please wait. " message appears and saving is
completed. Then, system environment setting screen appears again with all items
are disabled.
Note
Pattern 1 is set as factory setting.
16
E-
DMS2.5 has total 10 DI ports. However, actually used DI
ports are Ch1 and Ch2, and the rest of the ports (Ch3~Ch10)
are for additional functions. Therefore, make sure to
connect Ch1 or Ch2 when using it.
For DO, Ch1 and Ch2 are currently used inside of DMS2.5.
Ch9 and Ch10 are reserved in case of need. Therefore you
can only use Ch3~Ch8.