Transmitter MIM-B13A MIM-B13AC MIM-B13B Air Conditioner installation manual imagine the possibilities Thank you for purchasing this Samsung product. DB98-29543A(4)
Safety Precautions This installation manual indicates you to install the transmitter which is attached to the outdoor unit to use the centralized control. For installation of other optional accessories, see an appropriate installation manual. R ead this installation manual carefully before installation ...
Page 3
Transmitter Installation(For 64 indoor units) Accessories Transmitter MAIN Transmitter SUB �� �� �� �� �� �� 485 Communication DC Power Cable DC Power Cable Communication Cable Tie Case Cable (12V) (5V) Cable For certain types of outdoor unit, if the DC power cable provided with the transmitter can not be used, use the DC power cable provided with the outdoor unit.
Page 4
Transmitter Installation (Continued) Transmitter SUB PCB (BLU) (BLK) Channel 2 �� �� �� �� Channel 1 Outdoor unit PCB Transmitter ADDRESS Seting Switch Communication Cable between transmitter Terminal board DC 12V supply Transmitter ADDRESS Setting Switch �� �� DC 5V Channel 0 supply Transmitter MAIN PCB...
Page 5
Setting up Option Switches (Indoor Unit) In Case of Installing Centralized Control Only K1 K2 K3 K4 Adjust K2 DIP switch(SW05) on the indoor unit PCB to the 'OFF' position to enable centralized control. Set the RMC(1) and RMC(2) switch among the address setup SW05 switches of indoor unit main PCB as below.
Page 6
Transmitter Installation (Continued) Transmitter Classifying Flow Chart Select and install the transmitter according to the number of installed indoor units. If the number of indoor units connected to the outdoor unit is below 16 : Install the Transmitter MAIN PCB only. If the number of indoor units connected to one outdoor unit is ...
If the number of installed indoor units connected to one outdoor unit is below 16 Wiring Diagram Distance between the centralized control and the last transmitter should be 1000 meters or less. Indoor unit Indoor unit Indoor unit Outdoor unit 1 MAIN 0 RMC(1) 0 MAIN 1 RMC(1) 0 MAIN 2 RMC(1) 0...
Page 8
Transmitter Installation (Continued) If the number of installed indoor units connected to one outdoor unit is over 16 To install 48 Indoor units for 1 Outdoor unit (Individual control of indoor units) Centralized control Outdoor unit Power cable(DC 12V) Channel 2 Channel 1 Controls 16 indoor units ��...
Page 9
When setting the indoor unit address MAIN(TEN) MAIN(ONE) RMC(1) RMC(2) SW01 SW02 SW03 SW04 Indoor unit 3~12 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit MAIN(TEN) 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 RMC(1) Indoor MAIN(ONE)
Page 10
Transmitter Installation (Continued) To install 32 indoor units for 1 outdoor unit (Individual control of indoor units) Centralized control Outdoor unit Power cable(DC 12V) Channel 2 Channel 1 Controls 16 indoor units �� �� �� �� Power cable(DC 5V) with the RMC(1) switch set to '1' .
Page 11
When setting the indoor unit address MAIN(TEN) MAIN(ONE) RMC(1) RMC(2) SW01 SW02 SW03 SW04 Indoor unit 3~12 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit MAIN(TEN) 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 RMC(1) Indoor MAIN(ONE)
Page 12
Transmitter Installation (Continued) To install 16 indoor units for 1 outdoor unit (Individual control of indoor units) Outdoor unit Power cable(DC 12V) Channel 2 Channel 1 �� �� �� �� Power cable(DC 5V) Communication Cable Centralized control Transmitter �� �� Channel 0 Controls 16 indoor units with the RMC(1) switch...
Page 13
When setting the indoor unit address MAIN(TEN) MAIN(ONE) RMC(1) RMC(2) SW01 SW02 SW03 SW04 Indoor unit 3~12 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit MAIN(TEN) 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 RMC(1) Indoor MAIN(ONE)
Page 14
Transmitter Installation (Continued) To install 64 indoor units for 1 outdoor unit (Group control of indoor units) Outdoor unit Power cable(DC 12V) Channel 3 Channel 2 �� �� �� �� Power cable(DC 5V) Communication Cable Centralized controller Transmitter �� �� Channel 1 Controls 64 indoor units which have the indoor unit...
Page 15
When setting the indoor unit address MAIN(TEN) MAIN(ONE) RMC(1) RMC(2) SW01 SW02 SW03 SW04 Indoor unit 3~12 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit MAIN(TEN) 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 RMC(1) MAIN(ONE) 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5...
Page 16
Transmitter Installation (Continued) To install 19 indoor units for 1 outdoor unit + 13 indoor units for 1 DVM PLUS outdoor unit Outdoor unit Power cable(DC 12V) Channel 2 �� �� �� �� Channel 1 Power cable(DC 5V) Communication Cable Centralized DIP 1 control...
Page 17
When setting the indoor unit address MAIN(TEN) MAIN(ONE) RMC(1) RMC(2) SW01 SW02 SW03 SW04 Indoor unit 3~12 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit MAIN(TEN) 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 RMC(1) Indoor MAIN(ONE)