Capacity Tables; Cooling Capacity Tables - Daikin REQ71B7V3B Technical Data Manual

Split sky air outdoor units
Hide thumbs Also See for REQ71B7V3B:
Table of Contents

Advertisement

4

Capacity tables

4 - 1 Cooling capacity tables

FBQ71-125B7V3B + REQ71-100B7V3B
REQ71-125B7W1B
Cooling capacity table
Indoor
Outdoor
EWB
EDB
20
(°C)
(°C)
TC
SHC
SYMBOLS
AFR:
Air flow rate
BF:
Bypass factor
EWB:
Entering wet bulb temp.
EDB:
Entering dry bulb temp.
DB*:
Dry bulb temp.
TC:
Total cooling/heating capacity
SHC:
Sensible heating capacity
PI:
Power input
(comp.+indoor+outdoor fan motor)
Caution:
TC and SHC are shown by kW
V3: 230 V [50 Hz]
W1: 400 V [50 Hz]
• Outdoor Units • R-410A • REQ-B7
25
PI
TC
SHC
PI
TC
3
(m
/min)
(°CWB)
(°CDB)
(°CDB)
(kW)
(kW)
(kW)
• Split Sky Air • Outdoor Units
Outdoor temp. (°CDB)
32
35
SHC
PI
TC
SHC
PI
NOTES
1. Ratings shown are net capacities.
Influence of fan motor heat is included.
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.29 x 60 x AFR (m
/min.) x (1−BF) x (DB*−EDB)/860
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on following conditions:
Corresponding refrigerant piping length
Level difference
6. Air flow rate and BF are tabulated below.
Model
AFR
71
BF
AFR
100
BF
AFR
125
BF
7. Add the following corrections to power input of each model.
Model
Supply
V3
71
W1
V3
100
W1
125
W1
40
46
TC
SHC
PI
TC
SHC
3TW26592-2
: 7.5 m
: 0 m
FBQ
19
0.11
27
0.2
35
0.14
FBQ
0.11
0
0.19
0
0
37
4
PI
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Req71b7w1bReq100b7v3bReq100b7w1bReq125b7w1b