Installation
9 - 1 Installation method
37
9
REQ71∼125B7
Oil trap
Outdoor unit
NOTE:
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid
compression phenomenon, or cases of deterioration of oil return, it well be necessary to provide a trap at an appropriate
place in the riser gas piping.
A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.
30
• Outdoor Units • R-410A • REQ-B7
Oil trap
Gas piping
Liquid piping
• Split Sky Air • Outdoor Units
Indoor unit
4TW25149-8