Safety Device Settings - Daikin REQ71B7V3B Technical Data Manual

Split sky air outdoor units
Hide thumbs Also See for REQ71B7V3B:
Table of Contents

Advertisement

2
Specifications

2 - 4 Safety device settings

REQ71∼125B7
Model
Safety device
Fan motor thermal protector
HPS
LPS
Max discharge temperature
Overcurrent relay
• Outdoor Units • R-410A • REQ-B7
REQ71B7V3B
REQ71B7W1B
By thermistor and software control
By overcurrent sensor and software control
• Split Sky Air • Outdoor Units
REQ100B7V3B
REQ125B7W1B
REQ100B7W1B
Off 135 ±5°C
On 95 ±15°C
+0
Off 4,15
Mpa
- 0,10
+0,15
On 3.2
Mpa
- 0,15
+0,02
Off -0.03
Mpa
- 0,02
+0,03
On 0.05
Mpa
- 0,03
4TW26321-2B
37
2
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Req71b7w1bReq100b7v3bReq100b7w1bReq125b7w1b

Table of Contents