4.1

Installation requirements

Recommended protective devices
Recommended protection
L
UPS S1
N
L
UPS S2
N
After power connection, the Eaton ATS will automatically perform power-on self-test. After the test, the
Eaton ATS will start supplying power to its connected equipment. You can also press the 'Test Button' to
force the Eaton ATS to execute self-test.
Recommended Input and Output cord for EATS30H
Input power supply cord:
• UL Listed
• Non-detachable type
• Max. 4.5m (14.76 ft.)
• Min. 1.5 m (4.92 ft.)
• Type SJT
• SVT or SPT-2
• 300 V min.
• No. 10 AWG/3C.
One end terminates in NEMA L6-30P .
Output power supply cord:
• UL Listed
• Non-detachable type
• Max. 4.5m (14.76 ft.)
• Min. 1.5 m (4.92 ft.)
• Type SJT
• SVT or SPT-2
• 300 V min.
• No. 10 AWG/3C.
One end terminates in NEMA L6-30R.
ATS-01_EN
2 poles circuit breaker
L1
N2
2 poles circuit breaker
L2
N2

4. Power cables connection

S1
L
to the sensitive equipment
N
S2
ATS
Page 7